RA890 Series PRIMARY CONTROLS
The RA890 is a solid state electronic flame-safe- guard control for use with industrial and com- mercial gas, oil, and combination gas-oil burners and burners-boiler units. It responds to the rectification-type flame signal produced by any Honeywell rectifying flame-rod, rectifying photocell, or C7012A Ultraviolet Flame Detectors. Suitable for intermittent of interrupted ignition. Ignition is returned on flame failure to try to re-establish the flame. Provides automatic safety shutdown if flame is not established at start or is not re-established after flame failure. De-energizes fuel valve within 0.8 or 3 seconds depending on model. All models have SPDT contacts and termi- nals for connecting a 24 volt separately powered alarm that will sound when safety shutdown occurs. Mounts on Q270A1024 sub- base (order separately), and there-fore is a direct replacement for most RA890F controls. The RA890 will also replace the follow- ing obsolete models: R177, R180, R187, R190B, R887, R890B, R890C, RA190B, RA890C. RA890G has similar specifications, but is for use with Honeywell C7027, C7035, or C7044 “Mini- peeper” Ultraviolet Flame Detectors.
CAT. NO. MFG. NO.
1C530 1C532 1C533 1C534 2C984
RA890F1288 120 RA890F1270 120 RA890F1338 120 RA890F1346 120 RA890G1260 120
VOLTAGE FLAME RESPONSE TIMING 3
0.8 0.8 3 3
RA890F REPLACEMENT
To replace any RA890F control not listed here, select a replace- ment from this list by matching voltage, fl ame response timing, and safety timing to those of the obsolete control.
R4795 Series PROTECTORELAY
The R4795 provides electronic flame safeguard protection for commercial and industrial gas and oil burners. A choice of interchangeable
color-coded plug-in amplifiers permits the R4795 to be used with rectifying or ultraviolet type flame detectors. Plug-in timers permit selection of prepurge times. Amplifier and timer must be ordered separately according to needs of application. R4795D provides lockout on flame failure or flame relay pull-in during prepurge.
CAT. NO. MFG. NO. 1C579 1C580
1C581
1C582 1C584 1C578
DESCRIPTION
R4795A1016 R7289A1004
R7290A1001
ST71A1000 ST71A1018 Q270A1024
Primary control, 120v, 15 sec. safety
Amplifier (green). Use with Rectifying Photocell, Flame Rod, or C7012A
Amplifier (purple). Use with C7027A or C7035A Ultraviolet Flame Detector Purge timer---7 sec. Purge timer---30 sec. Subbase for R4795
EACH
$2,098.56 $589.65
$521.47
$209.59 $209.59 $167.44
CAT. NO. MFG. NO. DESCRIPTION 1C896
121708 EACH
Flame Simulator for RA890, R485 and most rectification controls
$123.15 TIMINGS EACH
15 15 30 30 15
$1,999.87 $1,968.34 $1,968.34 $1,999.87 $1,999.83
Q179 Series FLAME RECTIFIER GAS PILOT
Q179A is a combination pilot burner and rectifying flame-rod flame detector for interrupted or intermit- tent electrically-ignited gas pilot.
Q179D is a combination pilot burner and rectifying flame-rod flame detector with thermocouple adapter for standing pilot ap- plications.
CAT. NO. MFG. NO. 2C971 2C970 2C972
Q179A1050 Q179A1001
FLAME PATTERN EACH T Pattern T Pattern
Q179D1008 T Pattern
$351.32 $328.34 $157.52
Q270 Series MOUNTING BASE
The Q270A 1024 is a universal mounting base with dual markings on the terminals. It will
replace the Q267A1004, Q270A1008, and replace the Q267A1004, Q270A1008, and Q270B1007 bases. Base contains a complete terminal connection block for the specified control.
CAT. NO. MFG. NO. 1C578
USED ONLY WITH: Q270A1024 RA890F, RA890G,RA890H, or R4795 EACH $167.44
REPLACEMENT PHOTOCELLS AND VACUUM TUBES
A
B
C
D
Code Explanation: A = Vacuum tube; B = Photocell,lead sulfide, color coded white; C = Cadmium sulfide cell; D = Ultraviolet sensing tube.
CAT. NO. MFG. NO. CODE USED ON: 2C840 2C845 2C860 2C831
102988
104662D OC-10
129464N
A B C D
C7035 EACH
R478A, R4074A, RA190, RA890 C7015 C554
$114.17 $268.04 $7.78
$465.73
FLAME SIMULATOR
for RA890, R485 and most rectification controls
758