VERTICAL - CONTERFLOW (DOWNFLOW) MODELS WITH COPPER COAXIAL COILS CAT. NO. MFG. NO.
10G105 GT024B11LB1CA 2 10G105R GT024B11RB1CA 2 10G106 GT036B11LB1CB 3 10G106R GT036B11RB1CB 3 10G107 GT048B11LB1CC 4 10G107R GT048B11RB1CC 4 10G108 GT060B11LB1CD 5 10G108R GT060B11RB1CD 5 10G109 GT072B11LB1CD 6 10G109R GT072B11RB1CD 6
NOMINAL TONS SIDE RETURN CIRCUIT AMPACITY MAX. FUSE AMPACITY REFRIG. CHG. WEIGHT EACH Left
Right Left
Right Left
Right Left
Right left
Right
7.3 7.3
15.0 15.0 20.4 20.4 26.5 26.5 29.3 29.3
15 15 30 30 45 45 55 55 60 60
48 oz 48 oz 64 oz 64 oz 64 oz 64 oz 80 oz 80 oz N/A N/A
190 190 270 270 310 310 360 360 410 410
$8,298.00 $8,295.73 $9,490.00 $9,488.45 $10,081.87 $10,081.87 $10,675.25 $10,675.25 $11,743.39 $11,743.39
MFG. NO. DIMENSIONS H x W x D DUCT CONNECTIONS SUPPLY DUCT CONNECTIONS RETURN LOOP CONNECTION DESUPERHEATER CONNECTION FILTER SIZE GT024B 50-1/4 x 22 x 27-7/8” GT036B 54-1/4 x 26 x 32-7/8” GT048B 60-1/4 x 26 x 32-7/8” GT060B 60-1/4 x 28 x 32-7/8” GT072B 60-1/4 x 28 x 32-7/8”
12 x 14” 14 x 16” 16 x 16” 16 x 18” 16 x 18”
28.2 x 20.7” 30.2 x 25.7” 34.2 x 25.7” 34.2 x 25.7” 34.2 x 25.7”
3/4” 3/4” 1” 1” 1”
3/4” 3/4” 1” 1” 1”
30 x 24 x 1” 32 x 28 x 1” 36 x 28 x 1” 36 x 28 x 1” n/a
UNIT PERFORMANCE: AHRI DATA - GROUND LOOP HEAT PUMP
MFG. NO. CAPACITY HEATING BTU/HR
GT024A Full Load 22,200 Part Load 16,500
GT036A Full Load 31,400 Part Load 20,900
GT048A Full Load 45,500 Part Load 30,300
GT060A Full Load 52,200 Part Load 36,500
GT072A Full Load 59,700 Part Load 46,600
HEATING COP 3.7 4.2 3.6 4.5 3.5 4.3 3.5 4.3 3.6 3.5
COOLING BTU/HR 29,000 21,500 39,400 26,300 57,200 37,900 65,400 45,700 72,000 57,500
COOLING EER 16.0 20.0 18.0 24.0 17.6 23.8 17.4 23.6 14.1 19.1
Note: Rated in accordance with ISO Standard 13256-1 which includes Pump Penalties. Heating capacities based on 68.0°F DB, 59.0°F WB entering air temperature. Cooling capacities based on 80.6°F DB, 66.2°F WB entering air temperature. Entering water temperatures Full Load: 32°F heating / 77°F cooling. Entering water temperatures Part Load: 41°F heating / 68°F cooling.
GT024 GT036 GT048 GT060 GT072
UNIT PERFORMANCE: AHRI DATA - GROUND WATER HEAT PUMP
MFG. NO. CAPACITY HEATING BTU/HR
Full Load 25,500 Part Load 18,900 Full Load 36,100 Part Load 24,000 Full Load 52,400 Part Load 34,800 Full Load 60,000 Part Load 41,900 Full Load 68,600 Part Load 53,500
HEATING COP 4.1 4.8 4.1 5.2 4.0 4.9 4.0 4.9 4.1 4.0
COOLING BTU/HR 30,400 22,500 41,300 27,600 60,000 39,700 68,600 47,900 75,600 60,300
COOLING EER 18.4 23.0 20.7 27.6 20.2 27.4 20.0 27.1 16.2 22.1
Note: Rated in accordance with ISO Standard 13256-1 which includes Pump Penalties. Heating capacities based on 68.0°F DB, 59.0°F WB entering air temperature. Cooling capacities based on 80.6°F DB, 66.2°F WB entering air temperature. Entering water temperatures: 50°F heating / 59°F cooling.
272
Contractor Qualification Required – Limited Dealer Opportunities Available