Refrigeration System Troubleshooting usingSystemPressureandSuperheatMeasurements HEAD SUCTION HIGH HIGH LOW POSSIBLE PRESSURE PRESSURE SUPERHEAT CAUSE
Insufficient airflow across condenser
CORRECTION Check for dirty or damaged condenser coil
Check condenser fan operation
HIGH HIGH HIGH
System overcharged System overloaded
Evacuate and recharge
Check for proper equipment load sizing
Check for excessive humidity*
HIGH HIGH
HIGH LOW
VARYING LOW
Air in system
Insufficient airflow across evaporator
Evacuate and recharge
Check for dirty or clogged air filter
Check evaporator blower operation
Check for blocked or inadequate return air
Check for improperly sized duct system
HIGH LOW LOW LOW HIGH HIGH Restriction in liquid line System undercharged Restriction in suction line LOW HIGH LOW Overfeeding metering device
Locate and remove, evacuate and recharge
Evacuate and recharge
Locate and remove, evacuate and recharge
Check for moisture in system
Replace expansion valve LOW
LOW LOW
LOW LOW
LOW VARYING HIGH
System underloaded Incorrect refrigerant VARYING Faulty compressor valves
Check for proper equipment load sizing
Evacuate and recharge Replace compressor
* Effective system cooling capacity is reduced approximately 1000 BTUH per pint of humidity removal.