R8184 Series OIL BURNER PROTECTORELAYS
Provides automatic, non-recycling control of intermittent ignition oil burner systems. Used in conjunction with a C554A cad cell flame detec- tor and a 24v thermostat to switch line voltage to burner motor and ignition transformer.
External push button reset after safety shutdown. Includes solid state flame sensing circuit and 24v transformer to power heating control circuit; mounts on standard 4 x 4” junction box.
Electrical ratings: 45 second models - 7.4 amps @ 120v; 15 & 30 second models - 10.0 amps @ 120v.
CAT. NO. MFG. NO. 1C442* 1C444
1C445P 1C446
R8184G4025 45 seconds R8184G4009 45 seconds R8184G4066 15 seconds R8184G4074 30 seconds
SAFETY TIMING THERMOSTAT CIRCUIT EACH 24v 24v 24v 24v
* Use with W8684 for remote lockout indication.
$179.46 $154.73 $199.50 $199.50
C554 Series CAD CELL
FLAME DETECTORS
Light sensitive cadmium sulfide cell device. Will cause the primary control to shut down the oil burner upon flame failure.
R8184 Series
OIL BURNER PROTECTORELAY with Auxiliary Alarm Switch
Same functions and specifications as models shown above, but includes an auxiliary alarm switch for remote lockout indication.
Use with Q539A1394 (1C168) subbase which have lockout indica- tor lights or with Scully Scul-Tel® fuel monitor systems.
CAT. NO. MFG. NO. 1C440
R8184G4082 45 seconds
SAFETY TIMING THERMOSTAT CIRCUIT EACH 24v
$184.08
OIL BURNER STACK RELAYS RA116 & RA117 Series
Stack-mounted oil burner primary controls combine a protectore- lay unit for cycling and a pyrostat detector for sensing temperature changes of flue gas.
Shuts off burner upon flame failure, requiring manual reset; safety timing approx. 70 seconds. Element insertion adjustable from 3-1/2 to 5-1/2”; mounting by flat or curved flange provided. Manual trip safety switch to assure burner shutdown during servicing. Electri- cal rating: 7.4 amps @ 120v, 3.7 amps @ 240v.
RA117A - Flame or power failure followed by 1 minute scavenging period and one attempt to re- start, then lockout if flame is not re-established.
RA116A - Safety switch heater energizes upon flame or power failure, lockout occurs if flame is not re-established in 1 minute.
CAT. NO. MFG. NO. 1C500 1C504
RA117A1047 RA116A1055
THERMOSTAT TYPE IGNITION TYPE EACH 2- or 3-wire 2- or 3-wire
Interrupted Intermittent
Visit us at www.remichel.com
$360.23 $343.02
739
Mounts on burner blast tube or ignition transformer plate. Use with R4184, R8182, R8185, R8404 primary controls.
CAT. NO. MFG. NO. 1C400C 1C404
TM30S C554A1463 1C401
1C404C 2C860
C554A1794
TMK60 OC-10
DESCRIPTION Bulb & Holder Ass’y w/30” leads
Bulb & Holder Ass’y w/ 60” leads,3 mtg. brackets & oil line adapter
Bulb & Holder Ass’y w/60” leads & single parallel mounting bracket
Bulb & Holder Ass’y w/60” leads Replacement Cad Cell Bulb
EACH $19.90 $40.04
$26.22
$40.39 $7.78
R8184 Series
OIL BURNER PROTECTORELAY with Built-in Transformer for Cooling Controls
Same functions and specifications as standard mod- els, but includes integral 40VA, 24 volt transformer to provide power for a low voltage cooling control system, “Y” and “G” terminals for compressor and fan relay operation.
CAT. NO. MFG. NO. 1C447P
R8184M1051 45 seconds
SAFETY TIMING THERMOSTAT CIRCUIT EACH 24v
$288.74
CONTROLS