VERTICAL - COUNTERFLOW (DOWNFLOW) MODELS WITH PSC MOTORS CAT. NO. MFG. NO.
10G134 GS024A11LB0CA 2 10G134R GS024A11RB0CA 2 10G135 GS036A11LB0CB 3 10G135R GS036A11RB0CB 3 10G136 GS048A11LB0CC 4 10G136R GS048A11RB0CC 4 10G137 GS060A11LB0CD 5 10G137R GS060A11RB0CD 5
12 x 14” 14 x 16” 16 x 16” 16 x 16” 16 x 16”
Right Left
Right Left
Right Left
Right
12.3 12.3 19.4 19.4 26.1 26.1 29.7 29.7
25 25 40 40 50 50 60 60
48 oz 48 oz 64 oz 64 oz 64 oz 64 oz 80 oz 80 oz
190 190 270 270 310 310 360 360
NOMINAL TONS SIDE RETURN CIRCUIT AMPACITY MAX. FUSE AMPACITY REFRIG. CHG. WEIGHT EACH Left
$7,482.77 $7,482.77 $8,681.44 $8,681.44 $9,239.23 $9,239.23 $9,874.19 $9,873.92
MFG. NO. DIMENSIONS H x W x D DUCT CONNECTIONS SUPPLY DUCT CONNECTIONS RETURN LOOP CONNECTION DESUPERHEATER CONNECTION FILTER SIZE GS024A 50-1/4 x 22 x 27-7/8” GS036A 54-1/4 x 26 x 32-7/8” GS048A 60-1/4 x 26 x 32-7/8” GS060A 60-1/4 x 28 x 32-7/8” GS072A 60-1/4 x 28 x 32-7/8”
28.2 x 20.7” 30.2 x 25.7” 34.2 x 25.7” 34.2 x 25.7” 34.2 x 25.7”
3/4” 3/4” 1” 1” 1”
3/4” 3/4” 1” 1” 1”
18 x 36 x 1” 18 x 48 x 1” 20 x 50 x 1” 20 x 50 x 1” 20 x 50 x 1”
UNIT PERFORMANCE: AHRI DATA - GROUND LOOP HEAT PUMP
MODEL HEATING BTU/HR HEATING COP COOLING BTU/HR COOLING EER GS018 14,100 GS024 21,100 GS030 27,200 GS036 31,600 GS042 36,900 GS048 44,500 GS060 50,200 GS072 61,000
3.7 3.7 3.7 3.4 3.6 3.5 3.5 3.4
17,600 26,400 34,100 39,600 46,200 56,100 62,700 75,800
18.9 18.0 18.5 16.4 18.0 17.8 16.2 16.0
Note: Rated in accordance with ISO Standard 13256-1 which includes Pump Penalties. Heating capacities based on 68.0°F DB, 59.0°F WB entering air temperature. Cooling capacities based on 80.6°F DB, 66.2°F WB entering air temperature. Entering water temperatures: 32°F heating / 77°F cooling.
UNIT PERFORMANCE: AHRI DATA - GROUND WATER HEAT PUMP
MODEL HEATING BTU/HR HEATING COP COOLING BTU/HR COOLING EER GS018 16,200 GS024 24,200 GS030 31,200 GS036 36,300 GS042 42,400 GS048 51,100 GS060 57,700 GS072 70,100
4.3 4.3 4.3 3.9 4.1 4.0 4.0 3.9
18,400 27,700 35,500 41,500 48,500 58,900 65,800 79,500
21.7 20.7 21.3 18.9 20.7 20.5 18.6 18.4
Note: Rated in accordance with ISO Standard 13256-1 which includes Pump Penalties. Heating capacities based on 68.0°F DB, 59.0°F WB entering air temperature. Cooling capacities based on 80.6°F DB, 66.2°F WB entering air temperature.
270
Contractor Qualification Required – Limited Dealer Opportunities Available
AIR CONDITIONING & HEATING EQUIPMENT