CUT-OFF, CONDUCTIVE TYPE Series RB-24E
ELECTRONIC LOW WATER
for Hot Water Boilers Residential Applications with Self-Cleaning Probe
Series RB Low Water Cut-offs are uniquely designed to protect hot water boilers from the condition of low water. They provide burner cut-off in the event of a major loss of water, which can occur from a broken or leaking radiator, a cracked section in the boiler or other system problems.
Automatic reset feature resumes operation after a power outage. Maximum water temperature 250ÞF; Maximum water pressure 50 psi. 3/4” NPT male connection. For use on 24v systems only.
CAT. NO. MFG. NO. DESCRIPTION 3W215
144692 EACH RB-24E Low Water Cut-Off for Gas Fired Boilers $166.55 Series PS-800
LOW WATER CUT-OFF PROBE TYPE Series RB-120
for Hot Water Boilers Residential and Commercial Applications with Self-Cleaning Probe
Unit features electro-mechanical operation, automatic reset with no blow down required. Probe sensitivity 6,000 ohms at 120 VAC supply. Maximum water temperature 250°F; Maximum water pressure 160 psi; Maximum ambient temperature 120°F. 3/4” NPT male connections. Electrical rating 5.8 amps @ 120v, 2.9 amps @ 240v.
CAT. NO. MFG. NO. DESCRIPTION 3W216
144675 EACH RB-120 Low Water Cut-Off $236.06
ELECTRONIC LOW WATER CUT-OFF, PROBE TYPE
for Steam Boilers Residential and Commercial Applications with Self-Cleaning Probe
An inexpensive direct mount solid state control which uses the conductance of the boiler water to sense water level and shuts down boiler operation until level is restored. A 10-second timing feature allows for normal water turbulence during normal boiler operation and eliminates nuisance shutdowns.
Automatic reset allows boiler operation to resume as soon as water level comes in contact with probe (manual reset models are available on special order). LED low water indicator lamp shows when control is in low water shutdown mode. A separate terminal is provided for use with a 24 volt alarm or with a WF-2-U-24 water feeder.
Series RB-122-E
ELECTRONIC LOW WATER CUT-OFF, PROBE TYPE
for Hot Water Boilers Residential Applications with Self-Cleaning Probe & Test Button
The RB-122-E electronic Low Water Cut-off is easy to install and wire. Red low water indicating LED, green power indicating LED and automatic reset are just a few of the standard features. No blow down required. Maximum water
temperature 250°F; Maximum water pressure 160 psi. 3/4” NPT male connection. 120 VAC with 120v or 24v switching capacity.
CAT. NO. MFG. NO. DESCRIPTION 3W218
144676 EACH RB-122-E Low Water Cut-off $166.55 Visit us at www.remichel.com 463
Maximum boiler pressure 15 psi; Maximum water temperature 250° F. Maximum steam pressure 15 psi. Mounting connection is 3/4” NPT; probe length is 2-1/8” and requires 1/4” clearance from end of probe to boiler casting. Electrical rating 7.5 amps @ 120v, 3.75 amps @ 240v.
CAT. NO. MFG. NO. DESCRIPTION 3W234
3W234A
153917 153914
EACH
PS-801-24 Low Water Cut-Off PS-802-RX2-24 w/Remote Sensor
$295.90 $308.84
Note: Power is supplied by the boilers 24 volt transformer which must be of sufficient capacity.
Series PS-850
ELECTRONIC LOW WATER CUT-OFFS for Hot Water Boilers Residential, Commercial and Industrial Applications with Self-Cleaning Probe
Electronic operation with LED low water in- dicator light. No lock out with loss of power. No moving parts. No blow down required. Probe sensitivity 7000 ohms at 120 VAC sup- ply. 3/4” NPT connection. Maximum water temperature 250°F; Maximum water pres- sure 160 psi; Maximum ambient temperature
120°F. Electrical rating 7.5 amps @ 120v, 3.75 amps @ 240v. CAT. NO. MFG. NO. DESCRIPTION
3W283 3W285
153895 153896
PS-850 Low Water Cut-Off-120v EACH $315.32 PS-851-M-120 Low Water Cut-Off w/Manual Reset $393.71
HYDRONIC & STEAM SYSTEMS