Series 67
LOW WATER CUT-OFF, FLOAT-TYPE
for Steam Boilers Residential and Commercial Applications
For steam boilers of any size operating at pressures up to a maximum of 20 psi. Has 1/2” quick hook-up fittings for easy installation in
gauge glass tappings. Twin switch design provides an extra switch which closes upon a small drop in water level to engage a 101-A Electric Water Feeder without interrupting burner operation. Self- closing blow-off valve is standard. Electrical rating of switch is 7.4 amps @ 115v, 3.7 amps @ 230v. Model No. 67G is furnished with special low voltage burner switch terminals for use on self generating millivolt circuits.
CAT. NO. MFG. NO. DESCRIPTION 3W220 3W221
149400 149600
EACH 67, Low Water Cut-Off 67-G, Low Water Cut-Off, Millivolt Series 64
LOW WATER CUT-OFF, FLOAT-TYPE
for Steam Boilers Residential, Commercial & Industrial Applications
Features include adjustable BX outlet for easy installation, dual precision switches for dependable operation of the low water cut- off and alarm and electric water feeder, packless bellows, optional manual reset available, 1” NPT equalizing pipes required. Maxi- mum boiler pressure 50 psi. Electrical rating 7.4 amps @ 120v, 3.7 amps @ 240v.
CAT. NO. MFG. NO. DESCRIPTION 5G2186
143600 EACH 64, Low Water Cut-Off $511.25 Series 764
LOW WATER CUT-OFF, FLOAT-TYPE
for Steam Boilers Residential, Commercial & Industrial Applications
Features adjustable BX outlet for easy installation, dual precision switches for dependable operation of the low water cut-off and alarm or electric water feeder, packless bellows, 2-1/2” NPT side tapping provided for installation with close nipple. Maximum boiler pressure 50 psi. Electrical rating 7.4 amps @ 120v, 3.7 amps @ 240v.
CAT. NO. MFG. NO. DESCRIPTION 3W281
144500 EACH 764, Low Water Cut-Off $639.78
You will find an additional selection of... • Hydronic Controls in the Controls Section • Hydronic Valves in the Valves Section
466
$452.74 $452.74
Series 63
LOW WATER CUT-OFFS, FLOAT-TYPE
for Steam Boilers Residential and Commercial
Installs with 1” equalizing pipes. For boilers of any steaming ca- pacity. Features packless bellows. Optional manual reset available. Maximum boiler pressure 50 psi. Electrical rating 7.4 amps @ 120v, 3.7 amps @ 240v. CAT. NO. MFG. NO. DESCRIPTION
EACH 3W280 3W280M
142400 143100
63, Low Water Cut-Off 63-M, Low Water Cut-Off w/manual reset Series 69
LOW WATER CUT-OFFS, FLOAT-TYPE
for Steam Boilers Residential and Commercial Low Pressure Applications
Adjustable BX outlet for easy installation, dual precision switches for dependable operation of the low water cut-off and an alarm or electric water feeder.For mounting in 2-1/2” NPT boiler side tap- pings. Maximum steam pressure 20 psi. Insertion lengths: Model 69--4-1/8”, Model 169--3-1/8”. Electrical rating 7.4 amps @ 120v, 3.7 amps @ 240v.
CAT. NO. MFG. NO. DESCRIPTION 3W235 3W236
153900 155100
EACH
69, Low Water Cut-Off 169, Low Water Cut-Off
$368.68 $378.35
Series 150S
COMBINATION LOW WATER CUT-OFF/PUMP CONTROLLER
for Steam Boilers Commercial & Industrial Low or High Pressure Applications
Used to control boiler feed pumps directly from the boiler water level. Also includes a second switch at a lower level that can pro- vide low water alarm and cut-off. Maximum boiler pressure 150 psi. Installs with 1” equalizing lines. Completely packless con- struction with snap action switches. Electrical rating for pump and cut-off circuits: 7.4 amps @ 115v, 3.7 amps @ 230v.
CAT. NO. MFG. NO. DESCRIPTION 3W240S 150S
EACH 3W241S 150S-M 150-M, w/Manual Reset
150, Combination Low Water Cut-Off & Pump Controller $879.41 $879.41
Series 157S
COMBINATION LOW WATER CUT-OFF/PUMP CONTROLLER
for Steam Boilers Residential, Commercial & Industrial Low or High Pressure Applications
Essentially the same as the 150S model shown above but with an integral water column type float chamber equipped with all neces- sary 1/2” tappings for gauge glass set and tricocks.
CAT. NO. MFG. NO. DESCRIPTION 3W243S
157S EACH 150, Low Water Cut-Off w/water column $1,119.90
$627.39 $707.24