SPLIT SYSTEM AIR CONDITIONING CONDENSING UNITS, COMMERCIAL - R-410A
Combine with TAA series air handlers for new installations or use as a re- placement unit with existing compatible evaporators. Single high efficiency scroll compressors through 10-ton, dual compressors in 12.5-ton models. Copper tube/aluminum fin coils, loss-of-charge & high pressure controls, liquid line filter drier, time delay. Sweat connection service valves. 6-ton and 7.5-ton utilize PSC direct drive, totally enclosed fan motors with rain shields; 10-ton and 12.5-ton have two fan motors. Heavy-gauge, pre-painted steel cabinet provides superior corrosion and rust protection. Heavy duty steel base rails with unit lifting holes and forklift slots. All controls are pre-wired and located in separate compartment.
CAT. NO. MFG. NO.
COOLING NOM.TONS
10H825 TSA072S4SN1Y 6 10H826 TSA072S4SN1G 6 10H827 TSA090S4SN1Y 7-1/2 10H828 TSA090S4SN1G 7-1/2 10H829 TSA120S4SN1Y 10 10H830 TSA120S4SN1G 10 10H833 TSA150S4DN1Y 12-1/2 10H834 TSA150S4DN1G 12-1/2
COOLING BTUH 72,000 72,000 90,000 90,000
120,000 120,000 150,000 150,000
VOLTAGE PHASE
CIRCUIT AMPACITY
208/230-3 27 460-3
14
208/230-3 35 460-3
17
208/230-3 43 460-3
24
208/230-3 49 460-3
25
MAX. FUSE AMPS 45 20 50 25 70 40 60 30
ON COMPRESSOR
TS Series • 6 thru 12-1/2 ton cooling
ON PARTS
DIMENSIONS H x W x D CONNECTIONS LIQUID
48-3/4 x 39-7/8 x 48-3/8” 5/8” OD 48-3/4 x 39-7/8 x 48-3/8” 5/8” OD 48-3/4 x 39-7/8 x 48-3/8” 5/8” OD 48-3/4 x 39-7/8 x 48-3/8” 5/8” OD 48-3/4 x 60-1/8 x 43-5/8” 5/8” OD 48-3/4 x 60-1/8 x 43-5/8” 5/8” OD 48-3/4 x 60-1/8 x 43-5/8” (2) 5/8” OD 48-3/4 x 60-1/8 x 43-5/8” (2) 5/8” OD
CONNECTIONS SUCTION 1-1/8” OD 1-1/8” OD 1-1/8” OD 1-1/8” OD 1-3/8” OD 1-3/8” OD
(2) 1-1/8” OD (2) 1-1/8” OD
WEIGHT EACH
305 lbs $3,414.25 305 lbs $3,414.25 375 lbs $4,854.97 375 lbs $4,854.97 490 lbs $6,393.45 490 lbs $6,393.45 560 lbs $7,200.22 560 lbs $7,200.22
Note: All units use R-410A refrigerant, field supplied (units shipped with holding charge). Equipped to operate down to 30°F, addition of low ambient kit allows operation to 0°F.
ACCESSORIES FOR COMMERCIAL SPLIT SYSTEM AIR CONDITIONERS CAT. NO. MFG. NO. DESCRIPTION
USED ON:
10H860 47W16 10H861 47W17 10H862 47W18 10H863 44W17 10H864 44W18
Hail guard Hail guard Hail guard
TSA072, TSA090 TSA120 TSA150
EACH
$587.63 $587.63 $587.63
Low ambient control TSA072, TSA090, TSA120 $151.54 Low ambient control TSA150
$167.01
HIGH EFFICIENCY, SPLIT SYSTEM AIR CONDITIONING CONDENSING UNITS - 13 S.E.E.R. - R-410A - 3 PHASE
The 4SCU13LC series condensing units are built to achieve maximum ef- ficiencies while maintaining compact physical size. Units use high efficiency scroll compressors, are shipped with driers installed and are pre-charged for 15 ft. of line. Quiet top discharge design with enhanced copper tube with aluminum fin condenser coil. 208/230volt - 3 phase.
CAT. NO. MFG. NO.
COOLING BTUH
10H1087A 4SCU13LC136T 34,800 10H1088A 4SCU13LC148T 47,000 10H1089A 4SCU13LC160T 58,000
CIRCUIT AMPACITY 14.2 18.8 21.3
MAX. FUSE AMPS 20 30 35
29-3/4 x 24-3/4 x 26-3/4” 3/8” 37-3/4 x 29-3/8 x 31-1/4” 3/8” 33-3/4 x 29-3/8 x 31-1/4” 3/8”
ON COMPRESSOR
4SCU13LC Series • 3 thru 5 ton cooling
ON PARTS
DIMENSIONS H x W x D CONNECTIONS LIQUID
CONNECTIONS SUCTION 7/8” 7/8” 7/8”
WEIGHT EACH
202 lbs 220 lbs 282 lbs
ACCESSORIES FOR 4SCU13LC SERIES UNITS CAT. NO. MFG. NO. DESCRIPTION
10H818 34M72 10H814 40K58 10H819 45F08 10H379B 47J27
Low Ambient Operation Kit Blower Off Delay Kit
USE WITH EACH All Units All Units
Low Ambient Compressor Cut-off Kit All Units Short Cycle Protector
All Units Visit us at www.remichel.com 131
AIR CONDITIONING & HEATING EQUIPMENT