PRESSURETROL® CONTROLS PA404 Series
Steam pressure controller for 24, 120, 240 or self powered millivolt applications. Stainless steel diaphragm type sensing element; SPST snap-action micro switch.
PA404A - Used as high limit safety controller on steam boilers. Breaks control circuit at setpoint plus differential on pressure rise. PA404B - Used as fan controller on steam unit heaters. Makes circuit at setpoint plus differential on pressure rise. 1/4” FPT Con- nection. Electrical rating: 8.0 amps @ 120v, 5.1 amps @ 240v.
CAT. NO. MFG. NO. 2C550 2C552
RANGE
PA404A1033 PA404B1023
0.5 to 9 psi 0.5 to 9 psi
DIFFERENTIAL EACH 1 to 5 psi adj. 1 to 5 psi adj.
$228.55 $243.00
Note: Use 2K580, 2K581, 2K898 or 2K898A syphons with these controls.
L404F Series NON-MERCURY
PRESSURETROL® CONTROLS With many states now restricting the sales
of controls containing mercury, we have replaced the “L604A” pressure controls with the new “non-mercury” L404F series. These controls are SP-DT and are physically the same size and mounting as the “L604A” series.
Used as an operating, or limit control for pressure systems such as steam, air, non-combustible gases, or non-corrosive fluids. These controls replace L404A & B and L604 pressure controls. 1/4” FPT Connection. SP-DT Snap switch is rated @ 8.0 amps - 120 V and @ 5.0 amps - 240 V.
CAT. NO. MFG. NO. 2C586F 2C588F 2C590F 2C592F
RANGE
L404F1060 L404F1078 L404F1102 L404F1094
2 to 15 psi 5 to 50 psi
10 to 150 psi 20 to 300 psi
DIFFERENTIAL EACH 1 to 6 psi adj. 4 to 12 psi adj. 8 to 16 psi adj. 15 to 40 psi adj.
$228.34 $226.46 $236.08 $287.11
Note: Use 2K580, 2K581, 2K898 or 2K898A syphons with these controls.
L4079B Series NON-MERCURY
PRESSURETROL® CONTROL
This control provides manual reset limit protection for pressure systems such as steam,
air, non-combustible gases, or non-corrosive fluids. Trip free reset mechanism does not permit the limit to be over ridden by jamming the reset button. 1/4” FPT Connection. SP-ST Snap switch is rated @ 908 amps - 120 V and @ 4.9 amps - 240 V.
CAT. NO. MFG. NO. 5G758F
RANGE L4079B1033 2 to 15 psi
DIFFERENTIAL EACH Manual Reset
$206.45 Note: Use 2K580, 2K581, 2K898 or 2K898A syphons with these controls.
L608 Series VAPORSTAT® CONTROLLER
Operating and high limit controller for vapor heating systems up to 4 psi. May be used with liquids, air, non-combustible gases, oxygen or distilled water.
Stainless steel diaphragm type sensing element; SPDT mercury switch. Furnished with syphon loop, 1/4” MPT connection. Electri- cal rating: 8.0 amps @ 120v, 5.1 amps @ 240v.
CAT. NO. MFG. NO. 2C208
RANGE L608A1046 0 to 16 oz.
DIFFERENTIAL EACH 4 to 16 oz./sq.in.
$397.89
C6097A Series GAS/AIR PRESSURE SWITCH
The C6097A is a positive pressure, UL ap- proved, safety switch for use with natural gas, liquid propane gas, or air. Rated max inlet pressure is 5 PSI.
Diaphragm actuated SP-DT switch, automatic reset, 1/4” FPT con- nection. Electrical rating: 3 amps @ 120/240V.
CAT. NO. MFG. NO. 2C599
RANGE C6097A1053 2.0 to 21” WC
DIFFERENTIAL EACH 0.24 to 0.48” WC $123.81
L91 Series PROPORTIONAL
PRESSURETROL® CONTROL
Modulating control used as a high limit or as a direct controller for a proportional motor on pressure systems such as steam, air, liquid or non-combustible gases not harmful to brass bellows.
140 ohm potentiometer with screw adjustment on top of case. Electrical rating: 24v AC only. Connection: L91B1035, 1/4” MPT; L91B1050, 1/4” FPT.
CAT. NO. MFG. NO. RANGE 2C558 2C560
L91B1035 L91B1050
0 to 15 psi 5 to 150 psi
DIFFERENTIAL EACH 1 to 12 psi adj. 5 to 23 psi adj.
$441.88 $490.95
REPLACEMENT POTENTIOMETERS for Proportional Pressure Controls
CAT. NO. MFG. NO. DESCRIPTION FITS: 2C801
23176CF 140 ohm EACH L91B, -C all ranges $110.39
746
CONTROLS