HVAC Controls, Pneumatic • Air Station Equipment and Accessories
Model
Air Pressure Reducing Valve R-130
Description
The R-130 Air Pressure Reducing Valve is designed for use on compressed air systems to reduce the primary air to a desired pressure. A relieving feature reduces the output pressure when the output pressure setting is lowered. Excessive pressure buildup in a regulated pressure system is also prevented.
Used to control the pressure of the air delivered to pneumatic control systems. Models available for single- pressure systems or two-pressure systems (Day/Night or Summer/Winter) requiring two independently regulated pressure settings.
Features
• Built-in adjustable safety relief valve for limiting downstream pressure.
• For two-pressure models: Pressure changes accomplished with manual switch or automatically with electric pneumatic switch.
• Adjustable stops for desired settings item
PP901A1004 PP901B1002
inlet pressure range (psi) 45 to 150 psi
45 to 150 psi
output pressure range (psi) primary pressure: adj.0 to 25 psi.
primary pressure: adj.0 to 25 psi; secondary pressure: adj. 0 to 5 psi above primary rating
includes
Gage tapping to measure the regulated pressure
Gage tapping to measure the regulated pressure
682