Use to ignite pilots on commercial or industrial gas burners.
• Ignite gas pilots with spark gaps up to 1/4 in. (6.5 mm). • Reliable light off with 15,000 peak voltage. • Prevent detection of the ignition spark when properly applied in a flame detection system with the C7027, C7035 or C7044 Minipeeper Ultraviolet Flame Detector. • For use only in interrupted ignition applications. • Mount in same space used by conventional ignition transformer.
• Light weight, 3 lbs. (1.4 kg) versus 8-1/2 lbs. (3.9 kg) for standard transformers.
Item Q624A1014
Electrical ratings 120 Vac
Solid State Spark Generator Model Q652
Frequency 50 Hz; 60 Hz
A
DEsCrIPtIon
Use to ignite power gas burners in commercial and industrial applications.
FEAturEs
• Include single high voltage electrode for gas applications. • For use only with interrupted gas pilots with electrode spacings between 0.029 and 0.125 in. • Secondary Peak Voltage: 14Kv rms at 21Khz. • Mount in same space used by conventional ignition transformer.
• Prevent detection of the ignition spark when properly applied in a flame detection system with the C7027, C7035 or C7044 Minipeeper Ultraviolet Flame Detector.