Repairable Drip and Tracer Steam Traps Series C-500 and 546
DESCRIPTION
Designed for condensate removal in high pressure industrial, electric utility and marine systems, Yarway supplies a range of compact and easily maintained thermodynamic traps.Substantially smaller than comparable mechanical traps for high pressure application, the Yarway traps occupy minimal space in the piping. Heavy duty structural support is not required. Operation involves only a single moving part.
Ease of replacement of working internals also simplifies changing of capacity of any one trap merely by shifting to a differently rated set of internals.
Applicable Codes and Standards
Performance testing per ANSI/ASME PTC-39.1. End connections per ANSI B16.11 for socket-welding ends. How to Specify and Order
Typical Specification – The trap shall be Piston Valve Quick Change Trim Integral Strainer Impulse®
Trap. and
shall require neither bucket, bellows nor bimetallic element for operation.
Ordering – (1) Designate size of end connections (weights and dimensions table); (2) designate figure number; (3) designate trap internals (capacities curve); (4) designate “R” for commercial. Example: 1” 546 ASWR: (5) specify if ½” socket-weld strainer blowdown is required.
*Back pressure: to 25% of inlet psia
L
1110