Pneumatic Positioner Type AV1
DESCRIPTION The Type AV1 positioner is a control device that satisfies a wide range of applications. It provides fast, sensitive and accurate positioning of pneumatic single or double acting actuators. The AV1 receives an external pneumatic signal and converts it to a pneumatic output. This output produces the motive force that positions the power actuator. If a loss of signal occurs, the positioner goes to the 3 psi position. Type AV1 positioners can be equipped with either an optional potentiometric or a 4-20 mA position transmitter.
FEATURES
• Withstands vibration and shock at frequencies to 120 Hz and accelerations to 2G • Low air consumption
• Can control both single and double-acting, linear and rotary type actuators • Split range capability allows sequencing of multiple actuators using a single control signal • Simplified reverse operation
• Continuously adjustable span and zero for each stroke level • Adjustable speed control of actuator without additional hardware
• Standard model has high delivery capacity and Performance Series increases speed of response even more • Vent design allows natural gas operation • NEMA 4X version available • Optional manifold assembly
• Large array of accessories available to customize for specific applications
SPECIFICATIONS Input range¹ AV11 and AV15 AV12 and AV16
Accuracy² Resolution Hysteresis²
Repeatability² Deadband² Linearity² Weight
Operating temperature limits AV11/AV12 AV15/AV16
Storage temperature limits AV11 and AV12 AV15 and AV16
Humidity limits
20.7 to 103.4 kPa (3.0 to 15.0 psig) 20.7 to 186.2 kPa (3.0 to 27.0 psig) 0.80% of span maximum 0.09% of span maximum 0.45% of span maximum 0.12% of span maximum 0.12% of span maximum 0.70% of span maximum 1.84 kg (4.06 lb)
-40ºC to 82ºC (-40ºF to 180ºF)³ -20ºC to 127ºC (-4º to 250ºF)³
-40ºC to 93ºC (-40ºF to 200ºF) -20ºC to 127ºC (-4ºF to 250ºF)²
Operating and storage: 0% to 95% noncondensing
1. Units have 50% range suppression and/or zero elevation capability. 2. Tested according to ISA-S75. 13-1989.
3. For operation below 4.4ºC (40ºF), dew point of supply air must be 10ºC (18ºF) lower than lowest expected operating temperature.