This page contains a Flash digital edition of a book.
Table 26.6 Activity


Trenches


Assumed construction equipment used for noise calculations (BS 5228-1:2009) Scenario 1: Ducts


Scenario 2: Trenches and Ducts n/a Jointing pits HDDs


Telehandler 78dB 30T Excavator 75dB Loader 67dB Tractor & Trailer 79dB


n/a Haul Road


Loader 67dB D8 Dozer 86dB Grader 86dB Road Roller 80dB 9T Dumper 77dB 10T Excavator 75dB Tractor & Trailer 79dB Bowser 79dB Sweeper 76dB


Converter station


30T Excavator 75dB Dozer 86dB 9T Dumper 77dB Backactor Excavator 75dB Road Roller 80dB Telehandler 78dB Mobile Crane 78dB Static Crane 78dB 3T Dumper 77dB Scissor Lift 67db Concrete Pump 78dB


42.


30T Excavator 75dB Loader 67dB Trench Roller 80dB 9T Dumper 77dB Tractor & Trailer 79dB


Telehandler 78dB 30T Excavator 75dB Loader 67dB Tractor & Trailer 79dB


Driller Rig 79dB Crawler Rig 79dB Telehandler 78dB 3T Dumper 77dB


Loader 67dB D8 Dozer 86dB Grader 86dB Road Roller 80dB 9T Dumper 77dB 10T Excavator 75dB Tractor & Trailer 79dB Bowser 79dB Sweeper 76dB


30T Excavator 75dB Dozer 86dB 9T Dumper 77dB Backactor Excavator 75dB Road Roller 80dB Telehandler 78dB Mobile Crane 78dB Static Crane 78dB 3T Dumper 77dB Scissor Lift 67db Concrete Pump 78dB


*All noise levels are sourced from BS5228-1(2009) and are stated as LAeq @ 10m


It is assumed that the majority of construction works would be restricted to daytime working hours. The exceptions to this are likely to be the a) HDD drilling operations which, due to the nature of the drilling activity need to have the capacity to be undertaken continuously once drilling has commenced, and b) certain limited activities at the converter station including concrete pours.


43.


As an initial screening exercise, the distance from construction works at which the construction noise daytime lower impact threshold of 65dB LAeq 12hr would be exceeded was calculated. This ‘buffer’ distance, within which the construction noise limit is likely to be exceeded, is shown for the different construction activities in Table 26.7. The use of the 65dB LAeq 12hr construction noise limit is discussed further in the context of the baseline noise survey results in paragraph 100 below.


Preliminary Environmental Information May 2014


East Anglia THREE Offshore Windfarm


Chapter 26 Noise and Vibration Page 14


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58