SUPERMARKET SYSTEMS AND EQUIPMENT
Chilled food retailing – it’s horses for courses
T
he industry standard for the testing of refrigerated retail display cabinets, BS EN ISO 23953, states that tests on cabinets with glass doors should be conducted with 10 door openings per hour (every six minutes) with an opening/closing cycle of 15 seconds. Whilst door openings every six minutes may be representative of a low volume food retailing store, this frequency is not typical of the number of door openings in a busy supermarket or convenience store. There is little documentary evidence on the frequency of in-store door openings, but Orlandi et al (2013) claimed that the figure can reach 60 per hour in supermarkets and in 2011 EPEE and Eurovent stated that some
food retailers have registered up to 250 door openings per hour.
Doors are very effective when closed, but every time a door is opened cold air spills from the cabinet, compromising the holding temperature. In busy stores, with frequent door openings, cold air spillage is exacerbated, increasing warm air infiltration and the potential for raised cabinet temperatures. In short, the suitability of multi deck display cabinets with glass doors, for high traffic stores, is open to debate. To assess the implications of door openings on operating temperatures, refrigeration innovator, Adande, has conducted laboratory trials at its new state- of-the-art test facility in Lowestoft.
The tests compared the operating temperature of a commercially available multi-deck refrigerated cabinet, with factory fitted glass doors, against a comparable open front model, from the same manufacturer, modified with the Adande Aircell air flow management system. The trials were carried out under BS EN ISO 23953 conditions. Both cabinets were tested at an operating temperature of -1 to +4°C at climate class 25° C/60% RH (3M0).
After stable state running for 24 hours, the temperatures of ‘Tylose’ packs at corresponding positions in each cabinet were measured at 30 second intervals over a two-day period. To simulate a store environment, for a 12 hour period an automatic machine opened the glass doors 10 times per hour (every six minutes) with an opening/closing cycle of 15 seconds. The cabinet then operated for 12 hours without door openings. Temperatures recorded in the cabinet with glass doors had a range of 5°C. Significantly, the Aircell cabinet maintained a much tighter temperature band of just 3.5°C, representing a 30% improvement.
Following further stable state running periods of 24 hours, similar tests were conducted, over three days, with a door opening frequency of 20 openings per hour (every three minutes) for 12 hours followed by no door openings for 12 hours. During this regime, the temperature bandwidth
38 March 2017
www.acr-news.com
Page 1 |
Page 2 |
Page 3 |
Page 4 |
Page 5 |
Page 6 |
Page 7 |
Page 8 |
Page 9 |
Page 10 |
Page 11 |
Page 12 |
Page 13 |
Page 14 |
Page 15 |
Page 16 |
Page 17 |
Page 18 |
Page 19 |
Page 20 |
Page 21 |
Page 22 |
Page 23 |
Page 24 |
Page 25 |
Page 26 |
Page 27 |
Page 28 |
Page 29 |
Page 30 |
Page 31 |
Page 32 |
Page 33 |
Page 34 |
Page 35 |
Page 36 |
Page 37 |
Page 38 |
Page 39 |
Page 40 |
Page 41 |
Page 42 |
Page 43 |
Page 44 |
Page 45 |
Page 46 |
Page 47 |
Page 48 |
Page 49 |
Page 50 |
Page 51 |
Page 52 |
Page 53 |
Page 54 |
Page 55 |
Page 56 |
Page 57 |
Page 58 |
Page 59 |
Page 60 |
Page 61 |
Page 62 |
Page 63 |
Page 64 |
Page 65 |
Page 66 |
Page 67 |
Page 68 |
Page 69 |
Page 70 |
Page 71 |
Page 72