◾◽◽ Service door L/h DIN door hinge R/h DIN door hinge Bifold door
◾◽◽ Cable entry
Soft duct1) in both
side elements
Hard duct2) in both
side elements
Cable box3) in both
side elements Hard duct2) in top element Hard duct2) in base element
◾ ◽◽◽◽
1) Size of soft duct: approx. 267 x 165 mm. For fire protection reasons, the duct may be configured up to a max. of 60% with a maximum cable diameter of 15 mm and a maximum conduit diameter of 18 mm.
2) Size of hard duct: 2 panels each 120 x 120 mm. Cables up to a diameter of 15 mm may be routed through the hard duct.
3) Size of cable box: Field 1 approx. 210 x 44, field 2 approx. 210 x 25 mm. Cables up to a diameter of 15 mm and hoses up to a diameter of 44 mm may be routed through the cable box. No conduits may be routed through the cable box.
Locks Key lock with 2 keys Electronic combination lock1)
Electronic combination lock for activation via an access control system supplied by the customer
◾◽◽ 1) First code, second code and double code allocation possible. Key-based opening for inspection purposes supported.
TS IT rack with air baffle plates
Width mm
Height mm 2000 Depth mm 1000
2200 1000
600
2000 1200
2200 1200
2000 1000
2200 1000
800
2000 1200
2200 1200
◽◽◽◽◽ ◽◽◽
Supporting structure
Steel supporting structure to compensate for the raised floor height when siting the modular safe on the bare floor. The height of the support- ing structure is selectable between 100 mm and 1000 mm.
◾ Included with the supply ◽ Optional
Steel supporting structure to compensate for the raised floor height when siting the modular safe on the bare floor. The supporting structure has a fire-proof covering. The height of the supporting structure is selectable between 100 mm and 1000 mm.
◽◽
Rittal System Catalogue 35/IT infrastructure
Further technical information available on the Internet.