for LCP Rack/Inline CW To increase the cooling output, individual fan mod- ules may be retro-fitted into the LCPs. Additional integration can also achieve redundancy or reduce the electric power consumption of the LCP.
Packs of 1 pc(s).
Model No. 3311.011
The LCP 3311.130/.230/.530 (max. 30 kW) is supplied with one fan module as standard.
To achieve the max. cooling output of 30 kW, the customer/ service should install two addi- tional fan modules.
The LCP 3311.540 (max. 30 kW) is supplied with two fan modules as standard.
To achieve the max. cooling output of 30 kW, the customer/ service should install two addi- tional fan modules.
The LCP 3311.260/.560 (max. 55 kW) is supplied with four fan modules as standard.
To achieve the max. cooling output of 55 kW, the customer/ service should install two addi- tional fan modules.