Applications: – Cooling of IT equipment in IT enclosures sited as stand- alone units in secondary rooms
Benefits: – Even air distribution in front of the 482.6 mm (19") level
Functions: – The device supports front-to- back air routing typical of IT applications, and regulates the server inlet temperature to the set value
– The hot waste air from the IT equipment is drawn into the device at the rear of the IT enclosure, cooled, and the cooled air blown back in front of the 482.6 mm (19") level
– It is mounted on the roof of the IT enclosure, and cools the air volume inside the enclosure
IT monitoring: – Monitoring of incoming air tem- perature
Temperature control: – Control of the server inlet tem- perature
Material: – Sheet steel
Colour: – RAL 7035
Protection category IP to IEC 60 529: – External circuit IP 34 – Internal circuit IP 54
Supply includes: – Nano-coated condenser – Integral electric condensate evaporation
– Fully wired ready for connection – Drilling template –Air baffle plate – Assembly parts
Note: – A roof plate with cut-out to match the enclosure dimen- sions is required
For cooling IT equipment Model No.
Total cooling output L25 L35 W Total cooling output L35 L45 W Width mm Height mm Depth mm
Type of electrical connection Rated operating voltage V, ~, Hz Start-up current max. A Pre-fuse (T) A
Rated current max. A Refrigerant g
Permissible operating pressure (p. max.) bar Duty cycle %
Operating temperature range Setting range
Weight as delivered kg
Accessories Condensate hose
Door-operated switch
Air baffle plates for TS IT 482.6 mm (19") mounting angles Filter mats
1 pc(s). 1 pc(s).
3 pc(s).
Packs of
3301.800 3000 3200 597 417 895
Plug-in terminal strip 230, 1~, 50 36 16
9.2
R134a, 700 25
100
+10°C...+45°C +20°C...+22°C 97.0
3301.612 4127.010 see page 3286.500
464 755 812 454
Page
530
Further technical information available on the Internet.