Controlling vibration in diesel generators


GENSET VIBRATION CONTROL


Diesel generators are naturally prone to inducing mechanical vibrations. These undesirable vibrations are caused by the out­of­balance forces and gas fluctuations of the engine and vary depending on the number of cylinders, firing order and engine configuration, reports UKPN.


E


xcessive vibration in a diesel genera- tor can result in disturbances to adjoining structures and buildings, failure of components such as bearings, and reduced functionality of the generator, which can ultimately result in breakdown. Vibration control is therefore an important factor during the design and installation stages of any generating set. A typical 4 cylinder engine running at 1500RPM (25Hz) will have its dominant vibration harmonic at 2nd Order Frequency (i.e. 50Hz). This 2nd Order Harmonic is caused by the difference in inertia forces during the upward and downward stroke, due to the mass of the pistons. It is not possible to isolate 100% of the vibration caused by the generator, however with modern day balancing of engines and correctly-selected Anti-Vibration Mountings the vibration can be reduced by up to 99%.


Assuming that the engine has been correctly balanced, the first consideration should be the supporting structure that the generator is located on. This should be assessed by a structural engineer to ensure sufficient stiffness and rigidity. If the stiffness and rigidity is deemed unacceptable, or where high levels of isolation are required, an inertia base should be considered to increase the mass and hence increase the resistive inertia of the system. Secondly, the selection of Resilient Mounting should be conducted. This selection should consider the following factors: Dominant vibration harmonic of the engine; Running speed of the generator; Inertia forces of the generator; Total weight of the generator set; Combined centre of gravity; Mobile (portable) or static application; and


environmental factors (heat, contaminants etc.)


Based on this information a Vibration Control Engineer can calculate the natural frequency (fn) of the generator in all six modes of movement (known as “Six Degrees of Freedom – See Fig.1), consider other factors such as maximum strain on the rubber and the rubber type, and ultimately select a resilient mounting which provides optimum performance and fatigue life. Vibration reduction occurs by placing a flexible mounting between the generator and the supporting structure. This could be an ‘In- Skid’ installation where the mountings are placed in between the generator and the skid, or alternatively the mountings can be placed directly under the skid, fixed to the floor, known as an ‘outboard’ Installation. In some instances manufacturers will decide to use mountings both ‘In-Skid’ and ‘Outboard’ in an attempt to further improve the reduction of vibration.


There is a basic formula for calculating the un-damped natural frequency of the resilient mounting, and the level of vertical isolation based on the running speed of the generator. It should be noted that the formula can be used to calculate the isolation based on the primary running speed, or alternatively based on the dominant frequency, in which case the running speed should be multiplied by the corresponding harmonic to calculate vibration isolation efficiency.


The theory behind the above formula is based on the ratio between the disturbing frequency of the generating set and the natural frequency on the resilient mounting. Consider the example of a 4-cylinder engine with a running speed of 1,500RPM -


“The increased levels of


damping and higher levels of stiffness offered by Rubber


mounts give you increased control of the generator, particularly during Start­ Up, Shut Down, or if resonance


occurs. This increased damping and control


Fig.1:Six Degree of Freedom Modelling


however come at the expense of the vibration reduction which is


4-cylinder engine heads. 32


Fig.2: Typical Vibration Readout of a Generator Set.


typically lower than a Spring Mounting.”


Rubber mounts. Spring mountings


this will have a disturbing frequency of 3,000CPM or 50Hz, due to its 2nd Order Dominant Harmonic. A resilient mounting might be selected to give a vertical deflection of 2.5mm and the resulting vertical natural frequency will be 600CPM or 10Hz. The ratio between the disturbing frequency (50Hz) and the mounting’s natural frequency (10Hz) dictates the isolation efficiency.


Pure resonance occurs when the ratio between fn & fd equal 1:1 and isolation occurs when the ratio is higher than 1:1.44, with isolation increasing as the ratio increases.


For critical applications designers should consult with a Vibration Control Engineer to conduct a six degree of freedom model using dynamic stiffness and damping factors. Anti-vibration mountings are typically manufactured in two distinct types - Rubber Mounts and Steel Coil Spring Mounts. Rubber Mounts have comparatively high damping factors compared to Spring Mounts and also tend to offer lower levels of deflection (typically between 2.5mm-8mm). The increased levels of damping and higher levels of stiffness offered by rubber mounts provide increased control of the Generator, particularly during Start-Up, Shut Down, or if resonance occurs. This increased damping and control however come at the expense of the vibration reduction which is typically lower than a Spring Mounting. However, the majority of application rubber mountings still provide suitable isolation of up to 90%. Rubber Mounts are available with Captive Restraints to ensure a fail-safe design for mobile applications. Spring Mountings have a comparatively lower level of damping compared to Rubber mounts and generally provide high levels of deflection (typically 25mm, but can be up to 50mm). This high level of deflection results in extremely low natural frequencies, result in high levels of vibration reduction of up to 99%.


However the low stiffness of these products can cause issues during Start-Up, Shut Down, Resonance & Mobile applica- tions. Additional snubbers or restraints can be incorporated to control movement which could otherwise harm the spring mountings and any flexible connections. www.avindustrialproducts.co.uk


DECEMBER ‐ JANUARY 2017 UK POWER NEWS


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52