between the Guild of Architectural Ironmongers (GAI) and British Woodworking Federation (BWF). The scheme aims to educate and certify inspectors to check and verify the condition and legality of fire doors, ‘Essential’ items include: pivots or hinges, a door closing


device and/or a latch/lock (in lieu of the door closing device). These items are vital to maintain the integrity of the fire door in an emergency. Hinges, door closers, locks, latches and panic hardware are all considered essential ironmongery and must be CE marked for fire door applications as a minimum. CE marked products should be provided with additional certification by an approved third party such as CERTIFIRE. Other items of door hardware perform a function not directly associated with its fire performance (‘non-essential’), but they must not compromise the door's ability to withstand a fire for the specified time. All dedicated fire doors should be fitted with automatic clos-


ing devices conforming to BS EN 1154:1997 and be CE marked with third party approval as a minimum standard. An important factor is the closing moment: a fire-resisting door must be closed to be effective, and situations may arise, which dictate that a stronger door closer should be specified. In certain circumstances specialist devices are available, such


as panic and emergency escape devices. Panic hardware operated by a horizontal bar, must comply to BS EN 1125 where mem- bers of the public are present and have no prior knowledge of the exit or the hardware. Whereas BS EN 179 is an emergency appli- cation where the exit door is used by trained personnel and


PHOENIX HINGE SPECIFICATION FOR FIRE DOORS


Master hinge makers Cooke Brothers Limited, can provide a wealth of experience in supplying architec- tural hinges that both meet and exceed the required standards for hardware suitable for use on fire doors. Utilising the latest low friction maintenance free bearing designs that operate at well below the per- missible frictional torque requirements as stated in BSEN1935, ensuring the hinges have minimal impact on the overall functionality of the doorset, the


Phoenix range, including the popular Concealed Bearing and Shrouded Bearing ranges are specified widely where a “fit and forget” solution is required. Tested to BSEN1935 – up to Grade 14, CE marked and CERTIFIRE approved and sup- ported by third party fire test evidence to BSEN1634.


142


SAMSON 


  


  


 New  


advancing architectural ironmongery


www. simonswerk.co.uk t: 0121 522 2848 e: sales@simonswerk.co.uk


should only be used in low occupancy premises, where occu- pants are familiar with escape routes. Hinges fitted to fire-resisting doors should be able to achieve


the intended fire rating. The hinge should be able to allow the door closing device to close the door leaf from any angle to which it has been opened, overcoming the resistance of a latch or any seal when fitted. Door closers can put extra stress on hinges, which has significance for fire-resisting and escape doorsets. According to BS EN 1935, the door’s hinges must not be less than grade 2 and should withstand temperatures of up to 800oC. It’s important to note that all fire door components, such as


hinges, locks, door closers and vision panels, should be fitted with intumescent material to comply with the criteria within that item’s fire test certification and ensure the performance of the door. Fire doors are currently tested to BS476 part 22 or BS EN 1634, both of which require the test to be undertaken as a complete assembly including door leaf, frame, ironmongery, intumescent seals and glazing. Frequently, however, no intumes- cent is offered with the hardware product and subsequently may not be installed. This practice invalidates the CE marking of the product and the whole assembly. It’s essential to consider every detail when choosing architec-


tural ironmongery. Creating compliant premises is achievable with today’s innovative products and expert advice available. Ultimately, look for suppliers who stock the best range of prod- ucts with staff trained to GAI standards to receive the most up to date advice on products and industry standards.


141 COMAR 7P.I COMMERCIAL SWING DOORS


Comar Architectural Aluminium Systems is pleased to launch its next generation of commercial swing door sets. By taking the extensive range of solutions from its market leading Comar 7 Door range and coupling this with their trade-marked Comar Pi (polyamide insulation), the new Comar 7Pi Commercial Door offers even lower U-values housed in robust profiles for high traffic areas such as hospitals and schools. Safety and user friendly solutions are offered in the Comar


7Pi Commercial Door, with aesthetically pleasing round anti-finger trap stiles. Security concerns are alleviated as the doors have been extensively tested to PAS 24, offering compliance with the very latest security specifications. t 020 8685 9685 www.comar-alu.co.uk


143


TECTUS 


   


  


 New 


 144


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60