CASES & ENCLOSURES FEATURE
Enclosures protecting manufactuing
automation systems must have strictly controlled internal environments
cooling unit should be specified so that the average internal enclosure temperature of 35°C can be guaranteed under all load conditions and under all the ambient conditions that could be met at the machine’s location.
CHECKING THE ENCLOSURE TEMPERATURE The first check is to measure the temperature within the enclosure to assess its climate control capability. Temperature sensors should be placed in a position within the airflow of the enclosure, sensors should not be placed on or near direct airflow from high temperature components. Otherwise temperature readings can be found to be inaccurate. The sensors should be left to monitor the temperature trend
over a period of time. If the sensor records air temperatures of
well over 35°C (set point) then the output of the cooling unit should either be considered insufficient or, alternatively, that there has been a malfunction of the cold air routing in the enclosure. This means that the cooling air cannot reach (or can only partially reach) the temperature-sensitive components.
CHECKING THE CONTROL BEHAVIOUR OF COOLING DEVICES Another easy way of checking an enclosure climate control system is to observe the cooling unit’s control behaviour: Unlike speed-controlled cooling devices such as the new Rittal “Blue e+” cooling units, conventional enclosure cooling units
begin with the two-point regulation of the cooling operation when a temperature inside the enclosure gets above 35°C and finishes when the shutdown temperature of 30°C is achieved (at a typical hysteresis of 5K). If a cooling device does not reach the shutdown temperature, a conventional cooling unit will therefore continue to operate. If this happens, it is a good indication that the cooling unit has an insufficient output and suggest that there is likely to be a deficiency in suitable cooling air to the components inside the enclosure. You can simply touch a device to determine a refrigerator’s operating status: the activity of the refrigeration compressor during cold production is accompanied by a slight vibration of the refrigerator housing that can easily be felt. Alternatively, the exhaust temperature of the cooling unit in the external air circuit may be measured. During active cooling operation, this will be significantly higher (potentially, anywhere between 10° and 40°C) than the ambient temperature.
LOCATING HOTSPOTS You can also do a rough check of an enclosure’s climate control system with infrared thermography which measure the surface temperatures of the components inside the enclosure and these are recorded with an infrared camera. If any areas have significantly elevated temperatures (“hot spots”) it is an indication that they are not being supplied with enough cooling air.
Rittal
www.rittal.co.uk
IT INFRASTRUCTURE
SOFTWARE & SERVICES
www.rittal.co.uk
Page 1 |
Page 2 |
Page 3 |
Page 4 |
Page 5 |
Page 6 |
Page 7 |
Page 8 |
Page 9 |
Page 10 |
Page 11 |
Page 12 |
Page 13 |
Page 14 |
Page 15 |
Page 16 |
Page 17 |
Page 18 |
Page 19 |
Page 20 |
Page 21 |
Page 22 |
Page 23 |
Page 24 |
Page 25 |
Page 26 |
Page 27 |
Page 28 |
Page 29 |
Page 30 |
Page 31 |
Page 32 |
Page 33 |
Page 34 |
Page 35 |
Page 36 |
Page 37 |
Page 38 |
Page 39 |
Page 40 |
Page 41 |
Page 42 |
Page 43 |
Page 44 |
Page 45 |
Page 46 |
Page 47 |
Page 48 |
Page 49 |
Page 50 |
Page 51 |
Page 52 |
Page 53 |
Page 54 |
Page 55 |
Page 56 |
Page 57 |
Page 58 |
Page 59 |
Page 60 |
Page 61 |
Page 62 |
Page 63 |
Page 64 |
Page 65 |
Page 66 |
Page 67 |
Page 68 |
Page 69 |
Page 70 |
Page 71 |
Page 72 |
Page 73 |
Page 74 |
Page 75 |
Page 76 |
Page 77 |
Page 78 |
Page 79 |
Page 80