This page contains a Flash digital edition of a book.
ECO Compact Evaporators
EP Wall Evaporators
The EP range has been specifically designed for application in reach-in cabinets, display cases and small cold
rooms.
The entire range is equipped with high efficiency coils made from special profile aluminium fins and copper tube,
suitable for the new generation refrigerants. Dual fin spacing 3,5/7 mm.
For room temperatures down to -5 °C the electric defrost version is advisable, whereas for lower temperatures
( >-12 °C) an additional electric heater in the drip tray is recommended.
The standard fan motors employed have the following features:
diameter 230 mm, single-phase 230V/1/50-60 Hz and fibreglass charged polyamide fan guard;
IP 42 protection grade;
class B insulation;
internal thermal contact protection;
operating temperature -35 °C - +40 °C.
The versions with standard electric defrost (ED) are equipped with stainless steel heaters with vulcanised
terminals preset for 230V/1/50-60Hz connection.
The fan motors and the electric heaters of the EP/B models are pre-wired in IP 54 junction boxes.
For special applications and further information consult our Technical Dept.
Natural Defrost Model EP80-B EP100-B EP200-B EP300-B
Electrical Defrost Model EP80-BED EP100-BED EP200-BED EP300-BED
Nominal capacity kW 0.55 0.77 1.55 2.31
Capacity kW 0.46 0.63 1.28 1.91
Air flow m
3
/h 470 440 880 1320
Air throw m 2 2 2 2
Internal surface m
2
0.2 0.4 0.7 1.1
External surface m
2
2.9 4.3 8.6 12.9
Fan motors n° x Ø mm 1 x 230 1 x 230 2 x 230 3 x 230
Fan motor absorption A 0.35 0.35 0.7 1.05
Nominal power W 53 53 106 159
Circuit capacity dm3 0.6 0.9 1.7 2.5
Electric defrost W 300 300 600 900
Coil connections In (SAE) 1/2 1/2 1/2 1/2
Out (SAE) 1/2 1/2 5/8 5/8
Drain connection Ø (mm) 16 16 16 16
Net weight
1
kg 6.4 7.1 12.1 16.8
Dimensions - W/D/H mm 460x200x700 460x200x700 810x200x700 1160x200x700
Natural Defrost Code 3012 3013 3014 3015
Electrical Defrost Code 3016 3017 3018 3019
1
The weight refers to models with ED electric defrost.
X Use thermostatic valve with external pressure equalizer.
5
Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56
Produced with Yudu - www.yudu.com