This page contains a Flash digital edition of a book.
ECO Industrial Evaporators
ICE Industrial Range Ceiling Unit Evaporators
The ICE range has been specifically designed for use in large cold rooms and refrigerated storerooms suitable for the
preservation of fresh and frozen products.
The entire range is equipped with high efficiency coils made from special profile aluminium fins and inner grooved
copper tube, suitable for the new generation refrigerants.
In accordance to the room temperature the range is divided as follows:
ICE 06 for higher and medium temperatures (> -15 °C) with 6,0 mm fin spacing;
ICE 10 for lower temp. ( > -35 °C) with 10,0 mm fin spacing, the electric defrost ED version is recommended;
The standard fan motors employed have the following features:
450, 560 and 630 mm diameters, external rotor three-phase 400V/3/50Hz dual velocity, with epoxy coated steel fan guard.
IP 54 protection grade;
class B insulation (F for Ø 630);
internal thermal contact protection;
operating temp. -40 °C a +40 °C.
The versions with standard electric defrost (ED) are equipped with stainless steel heaters with vulcanised terminal preset for
400V/3/50-60 Hz connection.
The electric parts and casework are predisposed for grounding; the wiring of the heaters is carried out in separate IP 54
protection grade junction boxes.
On request the models can be equipped with non-standard coils, defrosting and fan motors.
For special applications and further information consult our Technical Dept.
Please check with our sales department for lead times, some of these coolers are made to order.
Model Identification
ICE 6 3 D 10 ED W84
Product identifaction
4 = 450 mm 5 = 560 mm 6 = 630mm
Number of fans
Heat exchanger reference
Fin spacing
Electronic defrost version
Circuiting ref. (brine-coolers only)
1
The weight refers to models with ED electric defrost.
X Use thermostatic valve with external pressure equalizer.
6 MM fin spacing coolers available up to 203 kW, 10 MM fin spacing coolers available up to 174 kW.
Please contact a Dean & Wood technical engineer at any of our branches for further information.
27
Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56