ECO Compact Condensers
Air Cooled Condenser Selection
Tab. 3
TD (K) 8 9 10 11 12 13 14 15 16 17 18 19 20
K1 0.53 0.6 0.67 0.73 0.8 0.87 0.93 1 1.07 1.13 1.2 1.27 1.33
K1* 0.46 0.54 0.62 0.69 0.77 0.85 0.93 1 1.08 1.15 1.23 1.31 1.38
Tab. 4
Refrigerant R407C R22 R134a R404a - R507
K2 0.87 0.96 0.93 1
Tab. 5
Inlet air temp degC 15 20 25 30 35 40 45 50
K3 1.03 1.02 1 0.99 0.97 0.95 0.94 0.93
Tab. 6
Altitude metres 0 600 800 1000 1200 1400 1600 1800 2000
K4 1 0.96 0.94 0.93 0.91 0.9 0.88 0.87 0.85
Tab. 7
Fin material Copper Aluminium Prepainted aluminium
K5 1.03 1 0.97
* For R407C and other refrigerants with high glide
38
Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56