Every second counts A


Interlinked fire detectors in domestic premises can give householders and firefighters more time when fire occurs


woman survived when fire spread through her


three-storey dwelling in Milton Keynes during the early hours of a July morning. She was alerted by a smoke alarm on the first floor.


However, she was prevented from escaping from the dwelling via the stairs, as the fire had already taken hold. Consequently, she became trapped on the second floor, where her shouts for help were heard by neighbours. The neighbours erected a ladder to a bedroom window,


providing the woman with a means of escape from this life-threatening situation. Their prompt action prevented her from becoming another fire statistic; in the financial year 2010-11 there were 321 fire-related fatalities in England, of which 212 were in dwellings1. Firefighters attended promptly at the scene but on arrival


were confronted with a well-developed fire on the ground and first floors, which had already resulted in destruction of the staircase at these levels. The smoke alarm that alerted the occupant was not


interlinked with other smoke alarms in the dwelling. The woman’s narrow escape and the potential risk to firefighters might have been avoided had a fire detection and fire alarm system having interlinked detector/sounder units been installed in accordance with BS 5839-6 (the Code of Practice for fire alarm systems in dwellings). Such systems are provided to give the earliest practicable warning of fire to occupants.


The importance of time The above incident highlights how important it can be to minimise the time it takes for the alarm to be raised to protect life and property when a fire occurs. Detecting fire and sounding the alarm at the earliest opportunity maximises the time available for occupants to take appropriate escape action and to contact the Fire and Rescue Service.


Fire detection and fire alarm systems For a typical dwelling, having two or three storeys with no floor exceeding 200m2 in area, a system consisting of smoke alarms (at least one appropriately-sited smoke alarm on every storey) and heat alarms (in the kitchen and principal habitable room, such as the lounge) will generally meet the recommendations of BS 5839-6, although this must be checked in detail against the requirements of that code of practice. The smoke alarms and heat alarms should generally be


interlinked, either by wiring or radio links, to ensure that the earliest warning of fire is provided to the occupants, as a fire detected by any detector element will produce an audible


SwitchedOn This article has been reproduced from the Winter 2011 issue of SwitchedOn, the quarterly magazine from the Electrical Safety Council (ESC). It can be downloaded from ESC’s website at www.esc. org.uk/industry/news-and- campaigns/switched-on/


warning by all fire alarm sounders in the dwelling. BS 5839-6 recommends a smoke alarm no more than


3m outside each bedroom door. In addition, where the designer identifies that the characteristics of the occupants place them at risk when a fire occurs, such as where occupants have deep sleep patterns due to the influence of drugs or have reduced ear sensitivity, alarms may be required within the bedroom to provide an adequate sound level likely to rouse them from sleep. Compliance with the recommendations of BS 5839-


6 is generally necessary in order to meet the applicable requirements of the building regulations in England and Wales, Scotland and Northern Ireland. Guidance on meeting those requirements is given in the associated Approved Documents in England and Wales, Technical Handbooks in Scotland, and Technical booklets in Northern Ireland.


Summary No life was lost in the incident described in this article because vital time to evacuate was provided by the individual alarm that roused the occupant. However, greater time might have been available for evacuation, and the fire damage to the property might have been reduced by the installation of a fire detection and fire alarm system having interlinked detector/sounder units in accordance with BS 5839-6.


References 1


Data reproduced from Department for Communities and Local Government and available at: www.communities.gov.uk/publications/corporate/ statistics/monitorq1q42011


November 2011 ECA oday


January 2012 ECA T Today


57


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64  |  Page 65  |  Page 66  |  Page 67  |  Page 68  |  Page 69  |  Page 70  |  Page 71  |  Page 72