This page contains a Flash digital edition of a book.
MECHANICAL CONTRACTING e Continued from p 50


safety factor compared to Supply Curve B (280 gpm) but an almost insignificant safety factor compared to Supply curve A (40 gpm). Some question whether a safety


engineering, and inspection/testing/maintenance, sprinklers systems have been successful due to “built in” safety factors including the following3:


and 602) and so on until all 17 sprinklers were flowing. The results are presented in Table 1. This analysis indicates that the first


sprinkler to operate provides 260 percent of the minimum design density. As more and more sprinklers operate, the density provided by each sprinkler naturally decreases, but, even with all 17 sprinklers operating, the most remote sprinkler still provides 110 percent of the design density. Not until the fourth sprinkler operates does any sprinkler deliver less than 0.2 gpm/sq.ft. With the entire density area flowing, the average density is 0.21 gpm/sq.ft., with the maximum density at Node 604 of 0.32 gpm/sq.ft.


Accounting for hose stream allowances


Figure 1: Impact of the variation in curve slope on safety factors 52


factor should be an amount of pressure or an amount of flow between the sprinkler system demand and the water supply curve. Since system flow and pressure are interrelated, the authors suggest that the safety factor should be the length of the line between the sprinkler system demand point and the point where the demand curve intersects the supply curve (see Figure 2). Equation 1 can be used to calculate the intersection of these two lines on a N1.85 logarithmic graph. Using this approach, a safety factor can be


Equation 1 Where: PJ =Pressure at junction point (psi) PS=Static pressure from flow test (psi) PR=Residual pressure from flow test (psi) QF=Flow from flow test (gpm) QJ=Flow at junction point


specified as a pressure or flow and will have meaning because it is measured as the pressure or flow component of the sloped line between demand and supply curves.


Inherent sprinkler system safety factors


Fire sprinkler systems have


enjoyed an enviable track record since the first sprinkler was invented in 1874. Beyond regulation, good


1. Initial densities are higher due


to the descending supply curve. 2. Calculations are started with the


design density requirement at the end sprinkler and inherently the average density in the system will be higher. 3. The hydraulically most remote


areas are calculated; any other configuration of sprinkler operation will produce higher delivered densities. 4. Calculations are developed on a


rectangular pattern, which is the most severe condition. 5. The friction coefficient for wet-


pip systems will probably average higher than the calculated C=120 resulting in higher delivered densities. 6. The hose stream demand


included in the total water supply is available to sprinklers in the early stages of a fire, further increasing the delivered density of the sprinklers. Safety factor No. 4 is


Figure 2: Safety factor measurements


illustrated in Figure 3. Safety factor No. 2 is best illustrated by the following analysis conducted by the authors on a light hazard wet-pipe sprinkler system in an academic building designed to deliver 0.1 gpm/sq.ft. over the most remote 1,500 sq.ft. The hydraulically most remote area contained 17 sprinklers. Successive sprinkler calculations were prepared that modeled the most remote sprinkler operating (Node 601), followed by the two most remote sprinklers operating (Nodes 601


Figure 3: Inherent safety factor due to sprinkler spray pattern


degraded water supply curve. This concept has been developed and promoted by J. Michael (Mike) Thompson, P.E.; a founding partner of the Protection Engineering Group. Mike has developed software providing a number of hydraulic tools, one of which plots supply vs demand curves in this fashion.


Density Concerning sprinkler system


design, fire protection professionals speak in terms of density; the rate of water application per unit area at the


3. “Rack Storage of Materials, NFPA 231C-1986.” IRInformation, Industrial Risk Insurers, February 1, 1990, 9.IN.10.1.2C. Sprinkler hydraulic calculations


are required to account for the water used by the fire department to manually suppress a fire. This is referred to as a hose stream allowance. Typically this is shown on a hydraulic graph as a line of a length equal to the allowance (in gpm) and extending horizontally from the maximum sprinkler demand. The problem with this depiction of the total system demand versus the supply is that the hose streams are not flowing at the maximum pressure demand of the sprinklers and not just at flows higher than the maximum sprinkler demand. In reality, the fire department is


“taking this amount of water away” from the available supply and the sprinkler system is “left” with a


phc june 2011 www.phcnews.com


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64  |  Page 65  |  Page 66  |  Page 67  |  Page 68  |  Page 69  |  Page 70  |  Page 71  |  Page 72  |  Page 73  |  Page 74  |  Page 75  |  Page 76  |  Page 77  |  Page 78  |  Page 79  |  Page 80  |  Page 81  |  Page 82  |  Page 83  |  Page 84  |  Page 85  |  Page 86  |  Page 87  |  Page 88