• • •   • • •   Heat Pumps – Type F or Type B RCDs?


fault current is > 10 mA, BS7671 requires the use of Type B – see 531.3.3 Note 3. For the benefit of Equipment Manufactures,


BS7671 Table A53 lists some basic configurations for different inverter topologies (Power Electronic Control System - PECS) and the associated Types of RCD. Manufacturers of self-contained equipment are responsible for testing and providing information on the operational AC leakage current (current flowing in the PE conductor). For standalone inverter drives, use motors, filters and inverters from a reputable company, who provided recommendations on RCD Type and sensitivity requirements.


RCD SENSITIVITY I


nverter speed controlled pumps and compressors circuits require specific Types of RCD. The characteristics of the inverter used to


control the speed, will determine if you require Type F or Type B RCDs and any associated restrictions on RCD sensitivity. Check with the Manufacturer of the standalone heat pump equipment before quoting for the installation.


BS7671 Regulation 531.3.3 details the


requirements for selecting the correct Types of RCD, based on the characteristics of the leakage current frequency and dc fault current components produced by the equipment.





Note: Type F or B RCDs must not be installed downstream of existing Type AC or A RCDs.


EQUIPMENT DESIGN CHARAC- TERISTICS AND INSTALLATION DESIGN


The selection of Type F or Type B RCDs is governed by the inverter topology and the value of the dc link voltage, which in turn determines the level of smooth dc residual current produced under certain fault conditions. Type F can be used < 10 mA smooth dc - see 531.3.3 Note 2. If the smooth dc 


 


The ac operational leakage current (PE current), must be compatible with the installation design and the RCD sensitivity requirements. Consider the possible addition of leakage currents, when adding new equipment to an existing installation, as this may require sub-division of existing circuits - see 531.3.2 (i). The total operational leakage current should not exceed 30% of the associated RCD sen- sitivity. This allows a safety margin for the effect of accepted levels of harmonics and normal supply voltage tolerances.


DOEPKE doepke.co.uk





  49  


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64  |  Page 65  |  Page 66  |  Page 67  |  Page 68  |  Page 69  |  Page 70  |  Page 71  |  Page 72