Three incidents caused by inadequately maintained electrical connections


ΒSEE (United States Bureau of Safety and Environmental Enforcement) has observed a recent trend of safety issues linked to inadequately maintained electrical connections that compromise wiring integrity.


This pattern has given rise to safety incidents, such as fires and arc flashes, underscoring the vital importance of averting these electrical hazards. Poor electrical connections pose a common and significant fire hazard, as they have the potential to generate substantial heat without significantly impeding electric current flow. This renders fuses and circuit breakers ineffective, allowing for escalation of the hazard. It is crucial to address these issues promptly and comprehensively to maintain a safe working environment.


Incident 1: Generator Cable Melting


Personnel conducting daily checks during a rainstorm heard a sudden popping sound, which prompted immediate investigations and revealed wires arcing at the junction box (400 Automatic Transfer Switch (ATS); for the gas generator. Personnel promptly initiated an emergency shutdown for the gas generator, activating the emergency diesel generator to supply power to the facility. Personnel strictly followed Lockout/Tagout (LO/TO) procedures as part of the emergency shutdown protocol. All valves to vessels on the facility were isolated and stop work authority was invoked to ensure immediate safety.


This incident involved a complete power loss of a temporary generator within the production facility. Upon investigation, the platform electrician identified that the 480-volt alternating current (VAC) phase cable had melted off at the generator bus connection. This was attributed to a loose cable connection at the cable lug. In response to the situation, power was switched over to the platform’s emergency generator. Fortunately, no injuries or damage beyond the wiring were reported. The root cause of the incident was traced back to the faulty cable connection at the cable lug, leading to excessive heat generation and subsequent cable melting.


Incident 2: Smoke and Cable Break


Personnel discovered that the top cable on the ATS from the platform diesel generator lacked a traditional drip loop. This absence allowed rainwater to flow onto the live power cable below, leading to its failure. Although designed to withstand weather, the improperly installed cable, exposed to constant sun and rain without adequate protection, developed small fractures in its casing. Over an undetermined number of years, rainwater seeped into the cable, causing material fatigue, and ultimately resulting in the cable’s failure during a thunderstorm.


In light of this recent trend, BSEE recommends, where appropriate, that operators and their contractors, consider the following:


- Implementing a routine inspection and maintenance schedule for cable connections to ensure secure and correct function.


- Ensuring that personnel involved in cable connections and maintenance receive proper training and understand the importance of secure and reliable connections.


- Communicating and rehearsing emergency response procedures, such as switching over to emergency generators, in case of power-related incidents.


This incident unfolded during a routine nighttime equipment check at a production facility. Crew members detected smoke emerging from a gap in the insulation near the inlet flange on the second flanged section of a fuel gas line run. An electrician was alerted and was able to take immediate action by turning off the breaker in the junction box, which supplied power to the heat trace section, ensuring a termination of all power. To prevent smouldering, the crew soaked the insulation with water. Upon subsequent investigations, a break in the heat


- Reviewing and enhancing existing procedures for connecting and securing cables.


- Reviewing and reinforcing LO/TO procedures to ensure the safe and secure isolation of electrical components during maintenance and investigations.


- Conducting periodic thermographic inspections using a forward-looking infrared (FLIR) camera to identify any signs of overheating or loose connections.


- Utilizing locking type connections in areas where fouling of electrical lines due to water ingress is a risk.


trace cable insulation on the inlet flange of the gas volume bottle was found. The root cause of this incident was traced back to the failure of the breaker to terminate power to the heat trace, attributed to improper grounding. This failure resulted in excessive heat and smouldering of insulation.


Incident 3: Arcing at generator junction box


THE REPORT | MAR 2024 | ISSUE 107 | 21


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64  |  Page 65  |  Page 66  |  Page 67  |  Page 68  |  Page 69  |  Page 70  |  Page 71  |  Page 72  |  Page 73  |  Page 74  |  Page 75  |  Page 76  |  Page 77  |  Page 78  |  Page 79  |  Page 80  |  Page 81  |  Page 82  |  Page 83  |  Page 84  |  Page 85  |  Page 86  |  Page 87  |  Page 88  |  Page 89  |  Page 90  |  Page 91  |  Page 92  |  Page 93  |  Page 94  |  Page 95  |  Page 96  |  Page 97  |  Page 98  |  Page 99  |  Page 100  |  Page 101  |  Page 102  |  Page 103  |  Page 104  |  Page 105  |  Page 106  |  Page 107  |  Page 108  |  Page 109  |  Page 110  |  Page 111  |  Page 112  |  Page 113  |  Page 114  |  Page 115  |  Page 116  |  Page 117  |  Page 118  |  Page 119  |  Page 120  |  Page 121  |  Page 122  |  Page 123  |  Page 124  |  Page 125  |  Page 126  |  Page 127  |  Page 128  |  Page 129  |  Page 130  |  Page 131  |  Page 132