EDUCATIONAL & STUDENT FACI LITIES
Figure 1
whilst providing new energy efficiency and safety capabilities. It is quite common for fume cupboards to have control capability already resident but not currently configured for operation. Contact the manufacturer of the fume cupboard, or a lab air management specialist, to investigate whether additional energy saving features on existing hardware can be brought into operation.
Step 6: Room air management For more significant energy reductions integrate fume cupboard air supply and extraction with the wider air management systems to prevent wastage. Installing a room air management system (such as the TROX EASYLAB system) makes it possible for all input and extract air for the laboratory to be controlled automatically to ensure that the required ventilation strategy and levels of safety are maintained. Supply and extraction of the fume cupboards (or other technical air management devices) is automatically balanced and offset in line with changing requirements, reducing the total supply and extract volumes.
For example, if the fume cupboards are open and extracting air, there is not the same requirement for the room system to carry out this process. By scaling down room exhaust air extraction in line with fume cupboard extraction, the room air management system is able to prevent wastage associated with over-supply of conditioned air, improving energy efficiency significantly (see Figures 1 and 2).
Step 7: Local heat extraction Equipment such as ventilated down flow tables, canopy hoods or fume exhaust ‘snorkels’ can reduce energy consumption by taking away heat at source, reducing loading on the site-wide cooling system.
Step 8: Tackle energy consumption out-of-hours A typical office space would require four air changes per hour. In the laboratory environment, due to the nature of the activities and substances present in the space, the number of air changes is typically set considerably higher to err on the side of caution.
www.tomorrowsfm.com
Figure 2
One energy-saving opportunity is to set the BMS (Building Management System) to reduce air change rates overnight or at the weekend when the laboratories are unoccupied, and the requirement for air changes is therefore lower. Local overrides can be used to ensure that, if personnel should be working out of usual work hours, the air changes can be re-established at times when the BMS has put the building into reduced mode.
Step 9: Check zoning Are you minimising overall energy consumption of the site by matching demand with supply? Look into the settings of different zones to check that the air change rates suit the activities carried out in each space.
Step 10: Optimise occupancy Room air management systems can reduce overheads by giving laboratory facilities greater operational flexibility. This enables multiple scientific disciplines to work side- by-side, reducing expensive under-occupation of the facilities.
www.troxuk.co.uk TOMORROW’S FM | 69
Page 1 |
Page 2 |
Page 3 |
Page 4 |
Page 5 |
Page 6 |
Page 7 |
Page 8 |
Page 9 |
Page 10 |
Page 11 |
Page 12 |
Page 13 |
Page 14 |
Page 15 |
Page 16 |
Page 17 |
Page 18 |
Page 19 |
Page 20 |
Page 21 |
Page 22 |
Page 23 |
Page 24 |
Page 25 |
Page 26 |
Page 27 |
Page 28 |
Page 29 |
Page 30 |
Page 31 |
Page 32 |
Page 33 |
Page 34 |
Page 35 |
Page 36 |
Page 37 |
Page 38 |
Page 39 |
Page 40 |
Page 41 |
Page 42 |
Page 43 |
Page 44 |
Page 45 |
Page 46 |
Page 47 |
Page 48 |
Page 49 |
Page 50 |
Page 51 |
Page 52 |
Page 53 |
Page 54 |
Page 55 |
Page 56 |
Page 57 |
Page 58 |
Page 59 |
Page 60 |
Page 61 |
Page 62 |
Page 63 |
Page 64 |
Page 65 |
Page 66 |
Page 67 |
Page 68 |
Page 69 |
Page 70 |
Page 71 |
Page 72 |
Page 73 |
Page 74 |
Page 75 |
Page 76 |
Page 77 |
Page 78 |
Page 79 |
Page 80 |
Page 81 |
Page 82 |
Page 83 |
Page 84