SENSORS & SENSING SYSTEMS FEATURE


FACTORS TO CONSIDER WHEN SELECTING AN INLINE THICKNESS MEASUREMENT SYSTEM


When selecting an in-process system for measuring the thickness of film, plate or sheet materials, a number of important factors need to be considered, including the effect of combined real world errors, says Chris Jones of Micro-Epsilon


I


n metals, plastics and rubber production, thickness (and width) measurement of


strip, plate, film and sheet is a key quality control parameter that needs to be carried out accurately and as the material is being processed. All manufacturers will have a process specification that they will need to meet in order to satisfy their customers. But in reality how can a manufacturer be sure that they are meeting these specifications at all times? A number of different measurement systems can be used to measure the thickness of a material. Some of these are used offline, i.e. random samples of the material are removed from production and measured to verify that they meet the specification. A more effective approach is to install an in-process or fixed, inline non-contact measurement system that continuously measures the thickness of the material as it is processed. If measurements from these systems move towards the outer limits of the specification, machine and process control parameters can be altered to bring the thickness back into acceptable limits.


BUILD IN-HOUSE OR PURCHASE A TURNKEY SYSTEM? The first factor to consider is whether to design and build the measurement system in-house rather than purchase a turnkey system from a supplier. While there are many suppliers of sensors that can be mounted inline with simple framework and signals output to a local display or HMI for thickness calculation, verifying the actual measurement accuracy of this type of solution can be difficult. It is considered best practice to use a measurement system that is 10 times more accurate than the production tolerance. With many production tolerances reducing to below, for example <100 microns, it is therefore necessary to produce a measurement system with a capability of <10 microns, which is very difficult to achieve, particularly if the user has never done this before. Therefore going to a supplier of a turnkey system is often a more efficient solution.


What is important when selecting a


suitable system from a supplier is to understand the combined real-world errors that can occur when using a non- contact thickness measurement system and how these errors can be eliminated or compensated for. While many suppliers state on their datasheet that the measurement system meets a certain resolution and linearity, in the real world, this performance is affected by a number of environmental influences. Errors associated with real world thickness measurement are not always so obvious, but can combine to create significantly large errors. It is therefore critical to select a system based on system accuracy, not just sensor accuracy.


VERIFICATION OF SYSTEM CAPABILITY Look for a measurement system that provides fully automatic process capability (CPc, CPk, etc) features with in-built statistical functions that are available to the operator at the touch of a button. This should also include a store and print out feature that allows the operator to verify the material thickness at any time, with no supplier involvement required. It is extremely important to design a


mechanically and thermally stable sensor mounting frame. The mounting mechanism should be isolated from process or machine vibration as best as possible. Mounting with an O-frame is more stable than using a C-frame. Thermal expansion of mounting


materials is often overlooked as a source of large errors in precise thickness measurement. Therefore, selecting materials with as low a thermal expansion coefficient as possible is very important.


ERRORS DUE TO NON-ALIGNMENT Special attention must be paid to the alignment of the sensors, which are typically installed opposite one another. No misalignment, tilting or inclination of the sensors relative to the target object is permissible in order to ensure the sensor spots are measuring at the same point all the way through the measurement range.


/AUTOMATION


Position, measuring range, thickness


deviation and vibrations must be taken into account when the sensors are installed


For example, for a misalignment of 1mm and an inclination of 2°, there will be a thickness measurement error of 35µm. As a supplier of non-contact inline


thickness measurement systems, Micro- Epsilon has developed its own methods of precise sensor alignment (which took three years to develop) and patented algorithms for this process. In order to avoid thickness calculation error due to movement of the target, both sensors must be perfectly synchronised so that they perform the measurement at the same time, at the exact opposite point of the target.


POSITIONING OF THE SENSORS Position, measuring range, thickness deviation and vibrations must be taken into account when the sensors are installed. For correct thickness measurements, the target must always be located within the ‘measuring range’ of the sensors. If the target moves outside the measuring range at any time, this can lead to inaccurate measurements. In particular, any special operating conditions such as start, stop or speed changes must be carefully considered when positioning the sensors. Most thickness measurement


applications are either in a process/quality control environment where the object to be measured is fast moving, or in a ‘part inspection’ machine where the object is static and the laser sensors are scanning the part in as short a cycle time as possible. In both cases, it is important to match the laser measurement speed to the spatial resolution or cycle time required. Faster measuring rates are not always best as the laser sensor accuracy can suffer on difficult-to-measure surfaces.


Micro-Epsilon T: 0151 355 6070 www.micro-epsilon.co.uk AUTOMATION | NOVEMBER 2017 33


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64