This page contains a Flash digital edition of a book.
0.5m, the maximum length of installed cable and the highest power rating as given in Table 11.2 and summarised below:


• •


Up to 745km of inter-array (up to 75kv of alternating current) and HVAC export cables between collector and converter stations (up to 275kv).


Up to 620km of HVDC export cables (up to 600kv).


220. HVDC export cables may be rated between 320kV and 600kV. HVDC cables currently in use are restricted to 320kV and are most likely to be used for the East Anglia THREE project. However, 500kV designs are planned for deployment in the near future and due to the rate of technological change in this field and it is thought that there is a possibility that such cables or slightly larger may be available for the East Anglia THREE project.


221. During the operational phase AC cables (inter-array and export cables) would generate an electric field (E) and a magnetic field (B). The total E field cancels itself out to a large extent and the remaining E field is shielded by the metallic sheath and the cable armour. The varying magnetic field (B), however, produces an associated induced electric field (Ei); therefore both B and Ei fields would be generated by inter- array cables during the operational phase.


222.


Information on the predicted magnetic (B) and induced electric fields (Ei) from the range of cable types proposed for the project has been summarised in Chapter 9 Underwater Noise Vibration and Electromagnetic Fields, and is described in further detail in Appendix 9.1.


223. Whilst for the purposes of impact assessment it is appropriate to adopt a worst case approach, it is of note that EN- 3 guidance (paragraphs 2.6.75 and 2.6.76) states that EMF may be mitigated by the use of armoured cable and burial to sufficient depth (greater than 1.5m) means impacts are likely to be negligible. Therefore, once installed, operational EMF impacts are unlikely to be of sufficient range or strength to create a barrier to fish movement.


224. Normandeau et al. (2011) modelled expected magnetic fields using design characteristics taken from 24 undersea cable projects. Of the 10 AC and DC cables modelled, in eight of these it was found that the intensity of the field was roughly a direct function of voltage (ranging from 33kV to 345kV) although separation between the cables and burial depth also influenced field strengths. The predicted magnetic fields were strongest directly over the cables and decreased rapidly with vertical and horizontal distance from the cables (Table 11.29). The averaged


Preliminary Environmental Information May 2014


East Anglia THREE Offshore Windfarm


Chapter 11 Fish and Shellfish Page 74


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64  |  Page 65  |  Page 66  |  Page 67  |  Page 68  |  Page 69  |  Page 70  |  Page 71  |  Page 72  |  Page 73  |  Page 74  |  Page 75  |  Page 76  |  Page 77  |  Page 78  |  Page 79  |  Page 80  |  Page 81  |  Page 82  |  Page 83  |  Page 84  |  Page 85  |  Page 86  |  Page 87  |  Page 88  |  Page 89  |  Page 90  |  Page 91  |  Page 92  |  Page 93  |  Page 94  |  Page 95  |  Page 96  |  Page 97  |  Page 98  |  Page 99  |  Page 100  |  Page 101  |  Page 102  |  Page 103  |  Page 104  |  Page 105  |  Page 106  |  Page 107  |  Page 108  |  Page 109  |  Page 110  |  Page 111