Cable Management
Cable supports W
iring systems must be selected and erected to avoid during installation, use and maintenance, damage to the sheath or insulation of cables and their terminations (522.8.1). To ensure the requirements of this regulation are met, cables not installed in conduit or trunking are typically supported using a range of clips, saddles, band, glands and ties.
Requirements
All cables and conductors must be supported in such a way that the level of mechanical strain which naturally exists will not cause either the cable/conductor or the terminations to be compromised (522.8.5). Furthermore, all cable supports and enclosures shall not have sharp edges liable to damage the wiring system, and cable/conductors are not to be damaged by the means of fixing (522.8.11 & 522.8.12). It is important, therefore, that care is taken when selecting for use supports that are appropriate for the cable/conductors.
Types of support
There is a wide range of options available for the contractor when selecting cable supports. These include amongst other things: • Cable ties • Cable cleats • Cable clips • Cable tie accessories • Cable glands
The type of fixing will depend on the nature of the surface to which the support is fixed. For example, cable ties would be suitable for fixing cables installed on basket tray or cable tray, whereas cable clips would be suitable for wooden surfaces. Similarly, the type of support will depend on the type of cable being installed. For example, cable cleats will be suitable for steel-wire armoured cables.
Cable entry
Two issues must be addressed when cables enter an accessory: the risk of damage to the sheath/ insulation at the point of entry, and any potential strain on connections.
ewnews.co.uk October 2024 electrical wholesaler | 29
“Two issues must be addressed when cables enter an accessory: the risk of damage to the sheath/ insulation at the point of entry, and any potential strain on connections.”
Conclusion
All cables and conductors must be suitably supported to ensure that no undue strain exists on the cable or the terminations (522.8). Care should be taken to select appropriate support (clips, glands and the like) for cables and Unicrimp has a range of products to help the contractor in carrying out their duties.
Jake Green, head of technical engagement with Scolmore Group, takes a look at suitable means of cable support for a variety of circumstances, as well as the requirements of BS 7671, and provides wholesalers with a guide to appropriate cable support products to recommend to customers.
Where a cable enters a metallic accessory box having no protection from sharp edges, there is a risk that the insulation surrounding conductors may become damaged leading to arc and shock risk. Where cables enter a metallic accessory box, it is important that protection is provided, such as with rubber grommets or similar.
Even where cables entering an accessory box or other metallic enclosure are protected from damage, terminations may still be impacted by strain as cables are left unsupported. In such circumstances it is necessary for suitable support to be provided and compression glands provided to ensure the electrical and mechanical strength of terminations (522.8.5 and Note).
Page 1 |
Page 2 |
Page 3 |
Page 4 |
Page 5 |
Page 6 |
Page 7 |
Page 8 |
Page 9 |
Page 10 |
Page 11 |
Page 12 |
Page 13 |
Page 14 |
Page 15 |
Page 16 |
Page 17 |
Page 18 |
Page 19 |
Page 20 |
Page 21 |
Page 22 |
Page 23 |
Page 24 |
Page 25 |
Page 26 |
Page 27 |
Page 28 |
Page 29 |
Page 30 |
Page 31 |
Page 32 |
Page 33 |
Page 34 |
Page 35 |
Page 36 |
Page 37 |
Page 38 |
Page 39 |
Page 40 |
Page 41 |
Page 42 |
Page 43 |
Page 44 |
Page 45 |
Page 46 |
Page 47 |
Page 48 |
Page 49 |
Page 50 |
Page 51 |
Page 52 |
Page 53 |
Page 54 |
Page 55 |
Page 56