SUPPLEMENT FEATURE yMachine Safety


Detecting risky residual currents using


differential current measurement Residual currents in low voltage networks represent a fundamental safety risk, if they go undetected or if they are detected too late. They may cause operations to be interrupted unexpectedly, incurring damage to man and machine and in the final instance, leading to high costs


T


he watchwords in risk prevention are ‘detect early, warn and take action’. Permanent monitoring of residual currents is essential and is used to detect deterioration in the distribution system's insulation in a timely manner.The


residual current module for the Sineax AM/DM, Linax PQ and Centrax CU series is being introduced by Camille Bauer Metrawatt AG to detect residual currents in electrical systems. It provides an RCM (residual current monitoring) function as well as direct measurement of the earth conductor currents in electrical systems. The RCM function is based on Kirchhoff's First Law (Junction Law). This rule states that in a junction in an electrical network, the sum of the incoming currents is equal to the sum of the currents leaving the junction. If there is a difference caused by leakage current flowing through the earth, then a residual current is detected and reported. The operator is then requested to take action. The causes of residual current in a system can often originate in defective components, for example, in switching power supplies (LED lighting, computers, photovoltaic rectifiers, rapid charge points, etc.), or defective insulation in electrical connections and devices, defective PEN connections, etc.


Changing the channel In the optimum case, six current channels are used for monitoring, as shown here in the diagram. Channel five is used for RCM and channel six is used to directly measure the earth current (up to max. 1,000A). The residual current module lowers the safety risk in electrical installations in low voltage networks and provides an early warning when gradual deviations occur. Measurement of residual currents is performed by residual current transformers. To provide this function, Camille Bauer Metrawatt AG has included residual current transformers to its product portfolio, in bushing-type and split-core


S10 June 2019 | Machine Safety


versions. An individual alarm threshold and early warning threshold can be defined for each residual current channel. When the alarm threshold is violated, or if the measurement (RCM) conductor is broken, this activates the device's group alarm. Additionally, in devices with a data logger, all status changes are logged in the alarm log and early warning threshold violations are recorded in an event list. The alarm signal can be routed to digital outputs and displayed by the Smartcollect database software. The residual current values that are currently being measured can be visualised directly on the device display or on the device website (WebGUI) and can also be output on analogue outputs. The values can also be read via bus interfaces. By recording the average value of the residual current, it is possible to detect a gradual change in the residual current. The advantages of permanent residual current monitoring are evident.


Saving money and risk On the one hand, it can eliminate costly periodic manual inspections, which only indicate the status quo at the time of measurement. On the other hand, continuous monitoring improves fire protection and also makes a significant contribution to protection against personal injury and damage to property. Applications for RCM, which is often in used in an energy metering and network quality analysis context, are frequently to be found in data centres, hospitals, hotels and other public buildings (for example shopping centres, airports, etc.), industrial installations, sensitive production units, banks etc. In such cases, to avoid any safety risk, threshold values in compliance with EN 62020 are applied (for example 100 mA).


CONTACT: Camille Bauer


Web: www.camillebauer.com Tel: 01543 469511


automationmagazine.co.uk


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64