Ancillary Rooms and Offices
Offices where specific tasks are carried out require higher temperature clean white, shadow free lighting. High uniform illuminance levels and balanced luminance levels on walls and ceilings will help staff to perform their job as effectively as possible. General Guidance is also available from the SLL Lighting Guide 7: Office Lighting.
Object Installation Project number Date
8 Office
Ancillary areas common to healthcare environments, such as canteens and rest areas can benefit from a more pleasant lit area, and the conventional illuminance uniformity requirements can be greatly relaxed.
8.2 Summary, Office 8.2.1 Result overview, Evaluation area 1
N y [m] LuxPanel Backlit Extra
• Area Dimension: 20.25 m2 • Lux Level Achieved: Lux 502 • Ceiling Height: 4.0m • Uniformity: 0.80U
• Luminaire Used: LBX66W42S40 – LuxPanel Backlit Extra Standard 31.5W
• Luminaire Layout: 2 Rows of 2 200 Wet Areas Climate Extra
• Area Dimension: 15.75 m2 • Lux Level Achieved: Lux 320 • Ceiling Height: 4.0m • Uniformity: 0.7U
• Luminaire Layout: 1 Rows of 2 Drawing1 Illuminance [lx]
Object Installation Project number Date
Wet Areas can be used to describe facilities such as plant rooms and stores, basically a room where there is increased risk of ingress of water or dust to the luminaire. High colour temperature, IP rated luminaires need to provide task lighting in the most practical way possible in these semi harsh lit environments with plant and laundry spaces lit to 300 lux at floor level as a guide.
6 Wet Room Climate Total luminous flux of all lamps Total power
General Calculation algorithm used Height of luminaire plane Maintenance factor
Total power per area (22.61 m²) Evaluation area 1 Em
Emin
Emin/Em (Uo) Emin/Emax (Ud) UGR (3.1H 2.9H) Position
Type No.\Make Luceco
10 4 Order No.
6.2 Summary, Wet Room Climate 6.2.1 Result overview, Evaluation area 1
y [m]0.80 0.70
Luminaire name : LuxPanel Backlit Extra Standard 31.5W Equipment
• Luminaire Used: LCL15066S40 – Climate Extra 5ft Twin LED Array 48W
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5
: 1 x LED 31.5 W / 4200 lm
16800.00 lm 126.0 W
5.57 W/m² (1.11 W/m²/100lx)
Reference plane 1.1 Horizontal 502 lx 400 lx
<=18.5 0.75 m
N
: : Example Care Home : : 13.11.2020
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5x [m] 300 500 750 1000
: : Example Care Home : : 13.11.2020
Average indirect fraction 2.80 m 0.80
: LBX66W42S40
Designed By Thomas Cotton Luceco PLC - Stafford Park 1, Telford TF3 3BD Page 17/17 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5x [m] 150 Exterior Environments Illuminance [lx]
Car parks, internal roads and unloading bays within healthcare facilities require functional lighting for safety but amenity areas can also be lit to enhance the exterior environment. Kingfisher Lighting, part of the Luceco Group, specialises in exterior LED lighting, including high-mast and street lighting systems and controls, as well as installation and maintenance services. Kingfisher’s dedicated team of lighting and mechanical engineers offer design expertise and are committed to environmentally accommodating external lighting needs with many products dark skies friendly with the use energy efficient technologies.
General Calculation algorithm used Height of luminaire plane Maintenance factor
Total luminous flux of all lamps Total power
Total power per area (17.28 m²) Evaluation area 1 Em
Emin
Emin/Em (Uo) Emin/Emax (Ud) UGR (2.3H 3.1H) Position
12 |
Type No.\Make Luceco
Reference plane 1.1 Horizontal 320 lx 244 lx 0.76 0.64
<=21.0 0.00 m
13200.00 lm 96.0 W
5.56 W/m² (1.74 W/m²/100lx) 200 300 500 750
Average indirect fraction 2.80 m 0.80
Page 1 |
Page 2 |
Page 3 |
Page 4 |
Page 5 |
Page 6 |
Page 7 |
Page 8 |
Page 9 |
Page 10 |
Page 11 |
Page 12 |
Page 13 |
Page 14 |
Page 15 |
Page 16 |
Page 17 |
Page 18 |
Page 19 |
Page 20 |
Page 21 |
Page 22 |
Page 23 |
Page 24 |
Page 25 |
Page 26 |
Page 27 |
Page 28 |
Page 29 |
Page 30 |
Page 31 |
Page 32