WC’s and Shower Rooms
Luminaires may be IP-rated where appropriate and the space lit to between 100-150 lux. Atlas
• Area Dimension: 2.00 m2 • Lux Level Achieved: Lux 113 • Ceiling Height: 2.8m • Uniformity: 0.88U • Luminaire Used: LBH214K – Atlas Bulkhead 24W 4000K
Over Bed Lighting
This is a multi-function area, with general lighting to 100 lux and luminaires to use lamps with a colour rendering capability of Ra80. Reading and general nursing will require around 300 lux, but a night light facility would also be required. Night lighting needs to achieve enough light for safe movement and to allow the nursing staff to check on a patient’s general condition.
Clean Rooms and Laboratories
Protection from the ingress of dust and liquids will often dictate IP rated luminaires that are easy to clean and maintain and 500 lux will be required at the working plane.
IP65 LuxPanel • Area Dimension: 126.00 m2 • Lux Level Achieved: Lux 507 lx • Ceiling Height: 2.80m • Uniformity: 0.84U
• Luminaire Used: LP66IP42S40 – LuxPanel IP65 Edgelit 600 x 600 40W Standard
• Luminaire Layout: 4 Rows of 5