WATER HYGIENE AND SAFETY
containing L. pneumophila may cause nosocomial Legionnaires’ disease was not proven, but the researchers suggested that it definitely warranted further study.11
Potable water contamination In 1985 Meenhorst et al conducted an investigation into an outbreak of nosocomial Legionella pneumonia. It revealed that the potable water of the hospital was contaminated with a distinctive strain of Legionella pneumophila (designated the Le-l strain), which was by culture and serology linked with human illness. To examine the possible role of this water in the outbreak, eight healthy guinea pigs were exposed to an aerosol of concentrated potable water. Seven animals developed pneumonia due to the Le-l strain of L. pneumophila. In one of these guinea pigs, the Le-l strain was also isolated from the blood and spleen. These results provided support to the theory that exposure of humans to aerosols of potable water contaminated with L. pneumophila may cause Legionella pneumonia.12
Again, in 1985, Garye Bollin et al conducted an air sampling test in showers and sink areas at the Youngstown Hospital, Ohio, in the US. A total of two paired water and air samples were obtained from each of the two shower rooms. All four water cultures grew L. pneumophila. Low numbers of aerosolised L. pneumophila (3 to 5 cfu/ 15 ft3
[0.43 m3 ] of air) were recovered
when the air was sampled above the shower doors with the six-stage sampler. Equal numbers of organisms were recovered in the first and second 15- minute sampling periods.
Hot water taps
A total of 19 paired water and air samples were obtained from 14 hot water taps. A total of 17 of the water cultures grew L. pneumophila. Two colonies of L. pneumophila (one on stage 1, one on stage 3) were recovered from air around one of the three taps tested with the six- stage unit. A total of 11 colonies were recovered (6 on stage 1, 5 on stage 2) from five of the remaining 13 taps tested with the two-stage unit. All positive air cultures from the two-stage unit were obtained during the period when the tap water was running. None were ever obtained before the tap water was turned on, or after it was turned off. No air cultures were positive more than once among the rooms that were tested two and three times.13
More recently, at the University Hospital of Brussels, the incidence of new patients with Carbapenemase-producing Enterobacteriaceae (CPE) rose from one case in 2010 to 35 cases in 2015. Environmental samples suggested that a contaminated washbasin was the source
40 Health Estate Journal February 2019
A toilet without a seat lid. Bio-aerosol production during toilet flushing was first reported in the 1950s.
of the outbreak. Besides other strains, Citrobacter freundii type OXA-48 was frequently isolated from patients and washbasins. To investigate the relationship between those strains, pulsed-field gel electrophoresis was performed. The strains isolated from patients and the washbasin in the implicated room were highly related, and pointed to sink-to-patient transmission. In total, 7 of 8 sinks in the isolation rooms of the ICU were found to be CPE contaminated. To control the outbreak, the washbasins and their traps and pipework were replaced with new ones. They were then flushed every morning with a glucoprotamin solution, and sink practice routines were improved, leading to discontinuation of the outbreak.14
Toilet flushing
Showers, taps, and washbasins, are not the only means of transmission via
aerosol. Toilet flushing is another significant risk area. Bio-aerosol production during toilet flushing was first reported in the 1950s by Jessen,15 who ‘seeded’ several types of toilet with Serratia marcescens (then termed Bacillus prodigiosus), and measured bio-aerosols produced by flushing. Agar-filled ‘settle plates’ caught bio-aerosols that fell out of the air because of gravity, and a Bourdillon slit impactor collected air samples. Cistern- fed, gravity-flow toilets and a mains-fed pressure-valve toilet were examined. In addition to colonies found on the floor- based settle plates, microbes were still being captured from the air eight minutes after the flush, indicating collection of ‘droplet nuclei’ bio-aerosols. Droplet nuclei are the tiny particles that remain after the water in a droplet evaporates. They have negligible settling velocity, and will float with natural air currents. Jessen observed that the amount of bio-aerosol increased with increasing flush energy. In 2005 Barker et al experimented with toilet bowls, and found that, although a single flush reduced the level of microorganisms in the toilet bowl water when contaminated at concentrations reflecting pathogen shedding, large numbers of microorganisms persisted on the toilet bowl surface and in the bowl water; these were disseminated into the air by further flushes.16
Faecal suspensions In 2011 Best et al17
performed in-situ
testing, using faecal suspensions of C. difficile to simulate the bacterial burden found during disease, to measure C. difficile aerosolisation. They also measured the extent of splashing occurring during flushing of two different toilet types commonly used in hospitals.
Decorative water features in healthcare facilities are now an additional ‘better-known’ area of risk.
Page 1 |
Page 2 |
Page 3 |
Page 4 |
Page 5 |
Page 6 |
Page 7 |
Page 8 |
Page 9 |
Page 10 |
Page 11 |
Page 12 |
Page 13 |
Page 14 |
Page 15 |
Page 16 |
Page 17 |
Page 18 |
Page 19 |
Page 20 |
Page 21 |
Page 22 |
Page 23 |
Page 24 |
Page 25 |
Page 26 |
Page 27 |
Page 28 |
Page 29 |
Page 30 |
Page 31 |
Page 32 |
Page 33 |
Page 34 |
Page 35 |
Page 36 |
Page 37 |
Page 38 |
Page 39 |
Page 40 |
Page 41 |
Page 42 |
Page 43 |
Page 44 |
Page 45 |
Page 46 |
Page 47 |
Page 48 |
Page 49 |
Page 50 |
Page 51 |
Page 52 |
Page 53 |
Page 54 |
Page 55 |
Page 56 |
Page 57 |
Page 58 |
Page 59 |
Page 60 |
Page 61 |
Page 62 |
Page 63 |
Page 64 |
Page 65 |
Page 66 |
Page 67 |
Page 68 |
Page 69