REFRIGERANT RECOVERY


Sponsored by


The key to F-Gas success


A good reclamation strategy can ease the transition to low GWP refrigerants, says Mel Summers of Climalife.


T 14


he F-Gas legislation requires recovery of HFCs from refrigeration and


air conditioning systems as mandatory, and also allows the continued use of reclaimed and recycled refrigerants with a GWP over 2500 for a further 10 years after the service ban on the use of virgin product on 01 January 2020. Reclaimed HFCs are ‘quota


free’ and therefore will be critical in playing their part in ensuring there is enough product available on the market to meet demand as the successive cuts in quotas impact upon availability. The big quota reduction in 2018 will be the first real test and EPEE (European Partnership for Energy and the Environment) has estimated that as much as 25% of the quota


shortfall will need to be met by product from reclaimed sources. By converting or replacing equipment running on higher GWP products such as R404A, R507 and R422D to much lower GWP refrigerants, the recovered product can be reprocessed and brought back to its original ARI specification. When recovered, the refrigerant is typically out of specification for moisture content, acidity and high boiling residue such as particulates, but it can be reprocessed and brought back into specification for reuse.


As part of the F-Gas Regulations


it is mandatory to recover all refrigerant from systems and in particular at end of life. Specially identified recovery


cylinders in a range of sizes are available for this purpose. The recovery must be done by those holding the correct qualifications for handling refrigerants, and in conformance with the hazardous waste regulations for documentation and transportation. Only if the recovered product does not leave site, and is returned to the system from out of which it came, does it avoid being classified as waste.


Reclamation of HFC refrigerant


means “the reprocessing of a recovered fluorinated greenhouse gas in order to match the equivalent performance of a virgin substance, taking into account its intended use”. The refrigerant is cleaned of all impurities to an AHRI 700 standard (the standard


required for virgin product), enabling it to be resold as regenerated product to the market. It will perform in exactly the same way as virgin product. Recycling is putting the recovered refrigerant through a basic cleaning process and usually means there is no analysis or quality assurance attached to the product in terms of specification or purity. It may not perform in the same way as virgin product, and the risk is with those using it. For peace of mind, best quality


and system operation, recovered product should be brought back to ARI specification by reclamation. For those companies who have more than one or several systems running on high GWP refrigerants either at the same site or across a number of sites, it is possible to convert equipment to lower GWP replacements one at a time, and have the recovered product reclaimed back to specification for use on systems not yet converted. If done in an organised and planned way, this can eliminate the need to purchase high GWP quota products at high prices and have the reclaimed product at a much reduced cost for when it is needed. There is no need to panic about moving away from high GWP refrigerants if a planned replacement programme is in place. Climalife is able to discuss Bespoke Reclamation arrangements to suit either the end user or a contractor looking after multiple sites.


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64  |  Page 65  |  Page 66  |  Page 67  |  Page 68  |  Page 69  |  Page 70  |  Page 71  |  Page 72  |  Page 73  |  Page 74  |  Page 75  |  Page 76  |  Page 77  |  Page 78  |  Page 79  |  Page 80  |  Page 81  |  Page 82  |  Page 83  |  Page 84  |  Page 85  |  Page 86  |  Page 87  |  Page 88  |  Page 89  |  Page 90  |  Page 91  |  Page 92  |  Page 93  |  Page 94  |  Page 95  |  Page 96