Bringing extra power to oil platforms


Containerised diesel generating sets are proving their worth in challenging environments, reports Frank Ponsonby.


W


hen working on a recent project for a customer requiring additional power on one of its oil platforms, a power supply expert encountered a rather considerable


challenge that needed to be overcome. Te main electrical power supply to the platform is imported over 40km from a third-party operator’s facilities through a 33kV subsea cable link. Under certain conditions, this link could be limited to 3MVA; less than sufficient for full production. To ensure sufficient power was always available to meet the requirements of full production, a key objective was the installation of two new offshore generators, each rated to deliver 2MVA Prime (continuous operation) of additional power. Dale Power Solutions supplied two containerised automatic start diesel generating sets (model MLE2500), each producing a continuous output of 2,500kVA, 2,000kW, 6,600V at 0.8 power factor. Prior to dispatch the assembled generating sets


were fully tested on resistive load banks. Drawings and documentation were included in accordance with the Supplier Data Requirements List (SDRL) specified by the client.


The engineered package Paul Roberts, Dale Power Solutions’ senior application engineer on this project, comments: “For this application, the generating set we selected was a V20 1,800rpm diesel engine with a prime power rating of 2740kW for generator applications with variable load. Electronic engine speed governing is included to meet Class A1 performance. Engine over-speed protection and emergency shutdown features are enabled by the installation of air intake shut-off valves on the set. Centrifugal lube oil filtration and duplex fuel filters are included for maintainability and reliability.” Automatic and manual start/stop control,


synchronising and load sharing is handled by Dale’s fully configurable generator set control system. A local generator touchscreen control switchgear panel is housed within the acoustic enclosure and a remote control panel is provided in the client’s switch room. Te ISO-style enclosure container has certified lifting lugs and is finished in a painting specification suitable for marine/offshore environments. It is


designed with acoustic lining and attenuators in the cooling air inlets and outlets. Rated performance in the ambient conditions of up to 45°C is achieved with the horizontally roof- mounted, electric motor-driven air-blast radiator. Airflow is managed with four redundant inverter- controlled fans fitted to the inlet plenum and designed to achieve twice the necessary combined airflow for cooling and combustion. Te roof-mounted radiator allows the basic external dimensions to be kept down to 13.5m x 2.44m while still allowing room for the roof- mounted nominal four-hour daily service fuel tank of 2,120 litres and the integrated fire and gas system.


Fig.1. Dale Power Solutions offers a range of generator systems that can be used in the most demanding environments.


Roof-mounted exhaust gas silencers with integral spark arrestors were produced from 304 stainless steel for durability in the offshore environment. Te enclosure’s fire and gas control panel with combined sounder beacons monitors the multiple UV flame detectors and flammable gas detectors installed on the container. Te control panel performs weighted monitoring to reduce false alarms. Detected flammable gas trips the motorised gastight dampers fitted to inlet and outlet apertures and shuts down the engine with the air intake shut-off valves. l


For more information ✔ at www.engineerlive.com/iog


Frank Ponsonby is business development manager, Oil & Gas, at Dale Power Solutions, Scarborough, North Yorkshire, UK. www.dalepowersolutions.com


www.engineerlive.com 33


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64  |  Page 65  |  Page 66  |  Page 67  |  Page 68  |  Page 69  |  Page 70  |  Page 71  |  Page 72  |  Page 73  |  Page 74  |  Page 75  |  Page 76  |  Page 77  |  Page 78  |  Page 79  |  Page 80  |  Page 81  |  Page 82  |  Page 83  |  Page 84  |  Page 85  |  Page 86  |  Page 87  |  Page 88  |  Page 89  |  Page 90  |  Page 91  |  Page 92  |  Page 93  |  Page 94  |  Page 95  |  Page 96  |  Page 97  |  Page 98  |  Page 99  |  Page 100