Fan coils
www.heatingandventilating.net Comfortably quiet
John Tarling, commercial manager of Dunham-Bush, explains the importance of acoustics and noise levels when selecting fan coil units
transmitted is known as the sound power level (SWL). In a similar manner to sound pressure levels, sound power levels are expressed on a logarithmic scale, in dB above the power corresponding to the threshold of hearing for a typical human ear. Sound power level (SWL) is given by SWL = 10 Log10 W / Wr where; W = sound power of source (W)
Dunham-Bush’s Panther fan coil unit
not require a large central plant to function and with simple proven, controllable technology and installation flexibility, they meet the demands of most commercial and domestic applications. One of the key factors influencing the choice of fan
F
coil units for buildings, such as offices or hotel bedrooms, is noise. As the selection of fan coil units is governed not only by thermal or air volume flow rate requirements, but also by any constraints on the level of noise permitted in the room, the manufacturer is frequently required to select fan coil units based on the predicted noise levels in the room because of the fan coil unit application. However these are influenced not only by the fan coil unit but also by the room itself. During the preliminary design stages, not all the room conditions may be known but certain assumptions allow the room noise levels to be approximated.
Sound pressure level
The human ear reacts to fluctuations in air pressure, which we hear as sound. The level of sound heard by the human ear (and measured by an acoustic meter) is known as the sound pressure level (SPL). The ear reacts logarithmically over a very broad range of sound levels and therefore sound pressure levels are quantified on a logarithmic scale relative to a reference sound pressure. They are expressed in decibels (dB) referenced to the pressure corresponding to the threshold of hearing for a typical human ear. Sound pressure level (SPL) is given by SPL = 20 Log10 P / Pr where; P = sound pressure being measured (Pa) Pr = sound pressure reference i.e. limits of hearing (2 x 10 -5 Pa)
Sound power level
In generating sound, the source will expend energy. The rate of transfer of acoustic energy from the source to the medium through which the sound is
28 February 2018
an coil units are a popular choice for engineers when selecting a reliable and efficient source of heating and cooling for a building. They do
Relationship between SWL & SPL
In simple terms, the SWL is the rate at which acoustic energy is transferred to a room from a particular source and the SPL is a measure of the resulting sound at a point within the space. A useful analogy is to consider a heater; the output of a heater is measured as power in Watts (W) and the effect of the output of the heater is measured as temperature in degrees Celsius (°C).
Sound path
It is important to consider that sound can be emitted from different sources to the listener. 1.Typically inlet and case radiated sound is transmitted through the ceiling into the room space. 2. In- duct sound is carried along the duct and through the supply air diffusers and radiates in the room space.
It is also important to consider that sound is transmitted via more than one route when in the room space. 1. The direct sound path is a straight path between source and listener. 2. Reverberant sound paths are any path, beginning at the source, along which sound is reflected off one or more surfaces prior to reaching the listener.
Room sound pressure levels
Certain criteria must be known to determine room sound pressure levels. Sound power levels of the fan coil unit – Sound power levels are typically specified as two separate sets of acoustic data, namely discharge in-duct sound power levels and inlet and case radiated sound power levels. Outlet ductwork – Size, length and type of ductwork together with the quantity of bends incorporated into it affect the level of discharge in- duct sound reaching the supply air plenum. Supply air plenum – Acoustic characteristics of supply air plenum is affected by its size, number of duct connections and whether or not it is acoustically lined. Supply air grille – Type and size of the supply air grille affects the level of the radiated discharge
70 60
Noise rating (NR) curves with typical SPL data plotted. Noise level in this case is said to be NR35
50 NR55 NR50 40
NR45 NR40
30
NR35 SPL
NR30 20 NR25 NR20 10 125 250 Oc Octave band centre frequency (Hz) 500 entr 1000 2000 4000
sound radiated into the room. High air velocities through the grille or duct may result in noise regeneration at an observed point. Position of the FCU and supply air grille – To prevent the cumulative effect of all of the radiating sources of noise, the sources should be separated to distribute the noise evenly. Ceiling construction – Level of inlet and case
John Tarling
radiated sound transmitted into the room space is dependent upon the insertion loss of the ceiling. Position of return path – This affects the inlet and
case radiated sound passing into the room. The return path should be installed as far as possible from the inlet to the fan coil unit. Room conditions and position of the listener – Sound pressure levels resulting from the direct and indirect mponent of sound transmitted from the ceiling and the grilles. The indirect or reverberant
sound path is affected by both the surface area of the room space and the sound absorption quality of the room surfaces. In addition, the direct path is affected by the distance between the observer and the source.
Noise assessment
Noise rating (NR) curves are the most commonly used method for assessing noise level in the UK. Each curve connects predefined sound pressure levels, which consider the response of the human ear at each of the octave bands. The noise level at a particular point in space is represented by the value of the NR curve whose constituent sound pressure levels are either less than or equal to those of the curve.
www.heatingandventilating.net
Noise level (dB)
Page 1 |
Page 2 |
Page 3 |
Page 4 |
Page 5 |
Page 6 |
Page 7 |
Page 8 |
Page 9 |
Page 10 |
Page 11 |
Page 12 |
Page 13 |
Page 14 |
Page 15 |
Page 16 |
Page 17 |
Page 18 |
Page 19 |
Page 20 |
Page 21 |
Page 22 |
Page 23 |
Page 24 |
Page 25 |
Page 26 |
Page 27 |
Page 28 |
Page 29 |
Page 30 |
Page 31 |
Page 32 |
Page 33 |
Page 34 |
Page 35 |
Page 36 |
Page 37 |
Page 38 |
Page 39 |
Page 40 |
Page 41 |
Page 42 |
Page 43 |
Page 44 |
Page 45 |
Page 46 |
Page 47 |
Page 48