FOCUS


Transmission risks


Number of cores with or without earth


1 1 1 1 1 1 1 1 1 1 1 1 1 1 1


Conductor size (mm2


)


BS 7671 and IEC 60364-5 method F current ratings for cables in trefoil in free air at:


10 16 25 35 50 70 95


120 150 185 240 300 400 500 630


3 and 4 2.5 3 and 4 4 3 and 4 6 3 and 4 10 3 and 4 16 3 and 4 25 3 and 4 35 3 and 4 50 3 and 4 70


Figure 1 Effects of temperature


Why is the test temperature for fire rated cables so important? Fire temperatures have adverse effects on electric cables and wiring systems. These include decreasing insulation resistance of dielectrics, material degradation of polymer based insulation and sheath materials which impact fixings and supports (especially for vertical installations). There are also fundamental changes to the


cables’ copper conductors, for example increasing conductor resistance, lowering of tensile strength, and oxidisation. Any current passing through a conductor will increase the temperature of the cable above


38 OCTOBER 2019 www.frmjournal.com


the surrounding ambient due to the electrical resistance of the conductor. If the ambient temperature is 30°C and the


conductor is required not to exceed 30°C, the cable will have a current rating (also referred to as ‘ampacity’) of zero amps. If the cable is in a fire (In the UK, we test fire rated power cables to 842°C, but with only a very small load and a three amp fuse), any significant current passing through the conductor will raise the temperature above the fire temperature of 842°C. This means that the conductor will be rather hotter than 842°C, and with the known reduction in insulation resistance performance of all dielectrics at these high temperatures, effectively these cables are not tested at the temperatures they are likely to operate at.


90oC 74


99


135 169 207 268 328 383 444 510 607 703 823 946


1088 32 42 54 75


100 127 158 192 246


Current rating for flexible fire rated cable in trefoil in a fire at:


950oC 1,000oC 49


66 88


108 141 171 216 253 298 347 412 491 581 704 848 20 26 34 47 66 88


108 141 171


30 40 53 65 85


107 130 153 180 209 249 296 350 425 511 12 16 20 28 40 53 65 85


107


Current rating for MICC cable in trefoil in a fire at:


950oC 53


71 94


117 148 182 226 266 313 361 434 491 639 - -


24 31 40 55 73 97 - - -


1,000oC 32


43 57 70 89


110 136 161 188 218 261 296 385 - -


14 19 24 33 44 58 - - -


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60