Emergency Power Emergency power in focus


Jenny Paramore, Product Marketing Specialist for ABB Emergi-Lite highlights the difference between Uninterruptible Power Supply (UPS) and Central Power Supplies (CPSs).


Why is it important to understand the difference between a CPS and a UPS?


emergency lighting in unexpected emergency situations. However, in recent months we’ve noticed that there has been a trend for electrical contractors to install UPSs instead of CPSs. The two types of system can look similar but there are important differences that mean that a UPS may not work as intended. The ongoing public enquiry into the Grenfell


C


Tower tragedy has highlighted the importance of ensuring health and safety systems are effective and fit for purpose. It’s therefore worth taking a few minutes to understand the technology and the regulations that are at play. This will ensure that emergency power systems are specified, installed and operated according to government legislation.


What is the role of a CPS or a UPS for emergency power applications? Both CPSs and UPSs can be used to supply backup power in the case of a power outage. The root cause of the outage may be due to unexpected circumstances like fire or explosion damage to the building itself or because of external factors on the power grid. In the case of the former, fire damage to


electrical equipment can lead to unusual fault currents on the network. As a result, the backup power supply must be able to clear these faults and then provide up to three hours of power for emergency lighting.


What is the main difference between a CPU and a UPS? Basically, CPSs are designed and built specifically for the role of supplying power for emergency lighting, whereas extra measures are needed to ensure that a UPS will meet the BS EN 50171 standard. With this in mind, the biggest difference


between the two technologies is that CPSs have a higher level of overload protection. This is provided by additional energy storage capacity than comparable UPSs. This gives a CPS the ability to operate a facility’s main switchgear and clear any high-level fault currents and disruptions. A good example of this is ABB’s Emergi-Lite EMEX battery system that typically delivers up to three and a half times the power of its output rating.


32 | electrical wholesalerJuly 2019


entral Power Supplies, also known as static inverters, have the essential role of providing backup power for


In comparison, when adopting a UPS for the


role, these units must be uprated to give them the ability to meet high power to operate the main switchgear as well as the longer-duration emergency lighting loads. Without this additional engineering work, the


UPS may not perform as expected should an emergency occur. This means that lighting and other safety systems may not work when they are needed most. The more typical application for UPSs is in data


centre and telecoms installations, where their role is slightly different. They provide back-up power over a few minutes, providing a bridge between the loss of mains power and the start- up of a standby generator.


Are there any differences to CPS and UPS in emergency lighting operations?


Once in operation, there is a legal requirement for emergency lighting systems to undergo periodic testing to ensure that they are working as anticipated. Being designed specifically for this role, CPSs


can integrate regular testing to meet the IEC 62034 fire safety standard. Manual testing can be expensive, time consuming and disruptive so the latest CPSs have an in-built capability to schedule and record the results of automatic testing of emergency lighting systems. Such automatic testing works by replicating a


power cut and then checking the performance of lighting circuits. Test results can then be automatically uploaded to a building management system. This provides the building


owner and manager with a complete and centralised record. For this to work, there needs to be a compatibility with the building management system such as BACnet and LONWORKS. This means that building owners and managers can keep reliable and consistent records and the system will send them an alert if they need to take action or plan any maintenance. In comparison, a UPS would need additional


engineering work to replicate these arrangements, adding hidden costs to the project. Alternatively, the building owner would need to provide additional administrative support for the entire lifetime of the installation to manage and record the results of fire safety tests.


What advice would you give the industry about emergency power systems?


While a UPS can be used in emergency lighting applications, a CPS is a smarter choice. It does not need additional engineering work to uprate it to deliver the high level of overload protection needed under the BS EN 50171 standard. In addition, many CPSs integrate automatic


testing to ensure straightforward compliance with the IEC 62034 standard. As a result, a CPS is a more straightforward option that gives reassurance that the installation is fit for purpose and will protect a building’s occupants without requiring extra configuration.


emergi-lite.com ewnews.co.uk


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60