search.noResults

search.searching

saml.title
dataCollection.invalidEmail
note.createNoteMessage

search.noResults

search.searching

orderForm.title

orderForm.productCode
orderForm.description
orderForm.quantity
orderForm.itemPrice
orderForm.price
orderForm.totalPrice
orderForm.deliveryDetails.billingAddress
orderForm.deliveryDetails.deliveryAddress
orderForm.noItems
WATER SAFETY PROCEDURES


60˚C Pump


60˚C


Calorifiers continuously pasteurise the water in the hot water circuit


20-45˚C Pump


20-45˚C


Under heavy demand calorifiers


cannot heat water sufficiently and pasteurisation does not occur


TMV


TMV


43˚C from tap


Demand rate from tanks does not exceed


mains input rate to tanks, so


tanks remain full Pump set


Path of least resistance


(temp. = 10˚C)


Stagnant cold water tank (temp. = 17˚C)


Legionella from tap


Parallel cold water tanks are difficult to balance


Demand from tanks exceeds mains input to tanks, so levels in both tanks drop, drawing stagnant water into service


Pump set


Stagnant cold water


Figure 1. Potential Scenario – Normal Demand.


tap for two minutes (standard practice) means that the water temperature being tested is approximately 50 metres from the outlet (because this is the amount of pipe ‘emptied’ by running a tap for two minutes, see Table 1).


Para. 7.30, ‘Drinking water’, suggests that separate drinking water systems are likely to have infrequently used outlets (because the volume of water necessary for drinking is small compared to the pipework volume). It would be possible for an Estates team to determine whether dedicated drinking water systems are present in a particular property. One might also expect a risk assessor to have recognised this and recommended elimination (but this almost never happens).


Appendix D.22, which relates to Pseudomonas aeruginosa, states: ‘Risk- assess the water system for redundant pipework and dead-legs (for example, where water is supplied to both the cold water outlet and a thermostatic mixing valve (TMV) supplying an adjacent blended water outlet, as such cold water outlets in augmented care units may be infrequently used)’. This is consistent with the statement I commonly make, that patients typically only use cold water to drink or clean their teeth. The drinking water tends to come from a jug. The washhand basin cold water is then only for teeth cleaning, which is likely to be done only at a few of the washhandbasins present. Clinical washhandbasins (i.e.


Figure 2. Potential Scenario – High Demand, e.g. during flushing.


those for staff) would probably never need separate cold water supplies. If drawings/schematics can be relied upon, then in principle an Estates team could predict these infrequently used outlets.


Impact of single-bedded rooms HTM.04 Part C,6


para. 2.1, acknowledges


that the provision of single-bed rooms with en-suites, and the promotion of hand hygiene, have increased the number of infrequently used outlets and low water throughput. It therefore makes sense to start any search for infrequently used outlets in wards which have single bedrooms with en-suites. The HTM guidance does not state who is responsible for identifying infrequently used outlets. Generally, health and safety law and guidance are based on the premise of ‘control and influence’. The water outlets in a ward/unit exist because the healthcare providers wish them to be present. The occupier has absolute control over whether or not those outlets are operated, and can identify those which are infrequently used. An Estates team can only effectively identify infrequently used outlets in the areas they directly control – plant rooms, their offices, workshops, etc. However, the Estates team has ‘influence’ in the sense that it may, during its routine activities, notice outlets which it suspects are infrequently used. It is bound by a duty of care to report these to the head of the ward/unit, for confirmation of their status, with a view to elimination or flushing.


Frequency of flushing


There is no difference between taps and showers. The previous guidance (HTM 04: 2006, Part B)7


How often should a shower or tap be flushed while in normal use and infrequent use conditions? The current frequency of flushing cited in guidance documents (which is the same for both showers and taps) is ‘weekly or as indicated by the risk assessment’,5 care units.6


and ‘daily’ for augmented recommended


twice-weekly flushing. Prior to that HTM 2040: 19938


only referred to flushing prior


to occupation and temporary closure of wards and departments, stating a duration of three minutes, and a frequency of weekly. There is a school of thought that says infrequently used outlets should be flushed until the temperature of the water is within critical control limits, which for hot water would mean 55˚C from the outlet (or inlet to a TMV). I have known people to flush outlets for as long as 10 minutes to achieve this temperature, which, as one can see from Table 1, could be the equivalent of emptying 200 metres of pipe. If it is taking that long to achieve a temperature, there is clearly something very wrong, and the flushing and ‘tick boxing’ are only hiding it. Particularly for hot water systems, it is important to study BMS plots of hot water calorifier temperature to verify that flushing exercises are not flattening the calorifier. Figures 1 and 2 illustrate the potential consequences of over-flushing a system. There is no particular benefit to flushing


November 2020 Health Estate Journal 57


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64  |  Page 65  |  Page 66  |  Page 67  |  Page 68  |  Page 69  |  Page 70  |  Page 71  |  Page 72  |  Page 73  |  Page 74  |  Page 75  |  Page 76  |  Page 77  |  Page 78  |  Page 79  |  Page 80  |  Page 81  |  Page 82  |  Page 83  |  Page 84  |  Page 85