PRIMARY LOW WATER CUT-OFF for Low Pressure Steam Boilers
Foam compensating probe type low water cut-offs for low pressure steam boilers (15 PSI max.) Features 15 second delay to prevent short cycling. “Probe Plus 30” feature allows water feeder (optional) to feed water 30 seconds above the probe to a normal operating level. Auto reset.
CAT. NO. MFG. NO. SUPPLY VOLTAGE PIPE SIZE EACH 3W410 3W412
CG450 CG400
120 24
3/4”MPT 3/4”MPT
SECONDARY LOW WATER CUT-OFF for Hot Water and Steam Boilers Manual Reset w/test button feature
For residential and commercial boilers. Burner circuit contacts open after 2 second delay in a low water condition. Burner circuit locks out if water remains below probe for 30 seconds. Manual reset will not trip out due to power fail- ures or air bubbles. Test button checks burner circuit to ensure proper control operation with-
out lowering water level. Can also be used as secondary cut-off on steam boilers and as primary cut-off on hot water boilers.
CAT. NO. MFG. NO. SUPPLY VOLTAGE PIPE SIZE EACH 3W405
550 120 3/4”MPT $372.98
MINI LOW WATER CUT-OFF for Residential Gas Water Boilers
Hydrolevel Company’s Safgard 1100 series low water cut-offs offer a 24 v space saving model and a 120v standard model. Safgard 1100 model is packed with features. On-board diagnostic power and low water lights simplify trouble shooting, while a burner circuit test button allows periodic tests of the control.
The 1100 model also includes a molex wiring harness with quick connect ends to easily adapt to virtually any boiler control setup. The 1100 model has a 5 amp max load switch with 24 volt control power. Due to its diminutive physical dimensions, the 1100 model can be mounted just about anywhere an opening ex-
ists on the boiler, or header. The 1150 model includes pigtails for quick wire nut connections. The 1100-H4 is special for Burnham O.E.M. usage. Burnham part #100106-01. The 1150 model has a 20 amp max load with 120 volt control power.
CAT. NO. MFG. NO. SUPPLY VOLTAGE PIPE SIZE EACH 3W399 1100
24
5W399B 1100-H4 24 3W398 1150
120
3/4” MPT $160.78 3/4” MPT
3/4” MPT $154.74 WATER FEEDER for Low Pressure Steam Boilers
The VXT is the first automatic steam boiler water feeder designed to monitor the amount of water added to a steam boiler. The addi- tion of make-up water raises the oxygen level in a boiler and accu- mulates lime and other mineral deposits. Excessive boiler make- up water can cause cast iron boilers to rest internally, severely shortening the boiler’s life.
Mineral deposits from too much make up water can impede heat transfer causing cast iron boiler sections to overheat and crack. Un- like any other water feeder, the VXT can protect the life of a boiler by exposing system leaks giving you the information you need to diagnose and repair the system before it’s too late.
CAT. NO. MFG. NO. SUPPLY VOLTAGE PIPE SIZE EACH 3W415 3W418
VXT-120 120 VXT-24
24
3/4”MPT 3/4”MPT
$466.33 $429.61
$328.18 $328.18
BOILER LEVEL & FEED CONTROLS
PRIMARY LOW WATER CUT-OFF for Water Boilers
Probe type low water cut-offs for residential and commercial hot water boilers automatically shut down the burner in event of a low water condi- tion. Auto reset.
CAT. NO. MFG. NO. SUPPLY VOLTAGE PIPE SIZE EACH 3W400 3W402
170 24
120 24
3/4”MPT 3/4”MPT
$192.76 $192.76
AUTO RESET LOW WATER CUT-OFF for Hot Water Boilers
This is a 120V powered LWCO with the capability of switching 24V, 120V, 230V loads.UL approved for auto reset applications on hot water boilers. Has SPDT switch for low water alarm and boiler shut down and an LED light to indicate low water conditions.
CAT. NO. MFG. NO. SUPPLY VOLTAGE PIPE SIZE EACH 5W120