HYDRONICS | FOLEY | CONTINUED FROM PAGE 48


measure the actual energy transferred by the ground loop. When I visited the site in early June, the ground loop was running at 58 F when the ambient temperature was 93 F. I left the most controversial issue for last. In studying


other passive house mechanical systems, I found that cooling was simply left to the ERVs or a ductless split or two. This project was a four-level American Foursquare with 4,600 sq. ft. in a climate with oppressively hot, humid summers. If I could not design a system that would control humidity, as well as keep the house cool in mid- July, this would be my first and last passive house design. I have since learned that this house is on the market for $1.7 million. Rest assured that whoever buys the house will have expectations of comfort as well as efficient, low- cost operation. If I could not deliver comfort, the latter point is moot.


50


In order to guarantee comfort at all times of the year, I felt it was necessary to design a ducted system with supply outlets in each room. The exceptions were the kitchen and baths,


The AC system was designed around a two-zone


The heat source is a Lochinvar Knight WHN055 wall- mounted condensing gas boiler (96% AFUE). This boiler has a low pressure drop fire tube heat exchanger and can modulate from 11–55 K Btu input. The low pressure drop also allowed the system to operate with only one Grundfos Alpha pump that only draws approximately 18 watts at design conditions.


system. We have used dozens of ERVs/HRVs in our past projects — mostly Renewaire and LifeBreath. Neither of these units was rated by Passive House Institute and would incur a rating penalty if used. Instead, we used a model from Zehnder that came with a high rating. The ComfoAir models we used have efficient cores and ECM motors that minimize electrical usage. This was the first time we used these, and we were happy with the quality of the product and support from Zehnder America. The two ERVs run continuously on low speed at all


times to provide adequate ventilation. Controls installed in each bath, as well as in the kitchen, allow the ventilation system to ramp up to any one of five speeds to ventilate quickly, up to a maximum of 200 cfm per system. We incorporated an experimental passive ground loop


to temper the incoming fresh air to the ventilation system. This is simply a 350' loop of 5


/8" PEX-a tubing buried in


the over dig around the foundation, approximately 8 – 10 feet below grade. A small Alpha ECM pump circulates a propylene glycol solution through this ground loop with an average temperature of 55 – 60 F. This fluid runs through a small heat exchanger that tempers incoming fresh air. It is important to use a heat exchanger with a drain pan and condensate drain as it will condense under certain conditions. I do not know what total effect this ground loop will


have on energy use, but it was relatively inexpensive and worthy of this experiment. We are in the process of data- logging this component to actually measure Btu transfer. We are measuring flow and delta-t across the loop to


ducted system with one air handler in the basement serving the finished basement and first floor and a second air handler in the unfinished part of the third floor attic serving the second and third floors. A Mitsubishi City- Multi S VRF (variable refrigerant flow) system was chosen for similar reasons as the boiler: low electrical draw and its ability to vary its output through its inverter drive compressor. This system can modulate from 30% — 100% capacity depending on load, or one — three tons. This was a more expensive solution, but I felt that this variable output was a critical design component. It was important not to oversize the system but to allow for capacity during high load conditions. I visited the site during an early heat wave we had in


late May. On a 102 F afternoon, the house was a cool, comfortable 74 F. I dropped the temperature down to 70 F to see how the system would respond under stress. The compressor ramped up, and the temperature started to drop inside. It passed my test. This system met all the specifications of passive house


design without compromising the comfort of the occupants. The system is flexible enough to respond to changing conditions without being oversized or short- cycling, yet has the horsepower to maintain comfort at extreme conditions. After working through this process over the past year, I better understand the concept of the passive house and expect it to expand in coming years. I am already working with Peabody Architects on their next passive house commission. Learn more about this project at this blog,


http://passivehouse.greenhaus.org/ or visit www.greenhaus.org/passive-house/ l


Dan Foley is owner of Foley Mechanical Inc. His


company has 14 full time and two part-time employees. His primary focus is on radiant and hydronics with large custom homes. Foley also does service, replacement, HVAC, sheet metal, controls, piping, renewables (geo and solar thermal) and services the Washington, D.C. metro area.


phc july 2011 www.phcnews.com


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64  |  Page 65  |  Page 66  |  Page 67  |  Page 68  |  Page 69  |  Page 70  |  Page 71  |  Page 72  |  Page 73  |  Page 74  |  Page 75  |  Page 76  |  Page 77  |  Page 78  |  Page 79  |  Page 80  |  Page 81  |  Page 82  |  Page 83  |  Page 84  |  Page 85  |  Page 86  |  Page 87  |  Page 88