ADDITIONAL CONSIDERATIONS FOR WIRELESS SYSTEMS If the digitised information is to be transmitted onwards using a wireless solution, there are other things that must be considered:


How will power be provided to the remote device? Simple devices may be able to operate from internal batteries for an acceptable period, but many wireless devices may still need cables to be laid to provide power and so not completely avoid the costs of wiring.


How immune is the radio technology to interference? How secure are the transmissions from eavesdropping, or from malicious actors blocking signals, or impersonating devices to provide false information?


Do the radios operate in controlled, licenced airspace, or do they use licence-free frequencies? If the latter, how is transmission to be guaranteed against accidental disruption by other systems operating in the same frequencies?


Digitising data implicitly places a constraint on the precision that can be recovered. Does the remote I/O device convert the data with enough resolution (i.e. number of bits) to be able to extract the nuances in the measurement required by any upstream analytics?


Is the quality of the measurement (accuracy, repeatability, noise immunity etc.) sufficiently good?


Transmitting data either serially or via a network takes a finite amount of time. This time is affected by the amount of data to be transmitted, the amount of protocol overhead needed to encapsulate the data, the speed of the communications media being used, and the number of other devices sharing the same connection. Can the data be recovered fast and sufficiently often enough to provide the necessary insights and avoid the risk of significant measurement spikes being missed if they occur between samples?


In transmitting data across communication networks, there is always a chance that a data packet may be delayed, received multiple times, or lost. How significant will any of these events be to the process being analysed or controlled?


Instrumentation Monthly October 2020


What are the ongoing costs of the communications provision? The costs of wired systems are normally limited to the capital cost (Capex) of purchasing and installing the equipment, but many radio-based systems involve an ongoing operational expense (Opex), for example for cellular service provision.


Can reliability be improved by adopting systems with radio diversity with the chosen technology (i.e. automatic routing of signals via multiple path options, for example as found in ‘mesh’ systems)?


What is the working range of the wireless technology in the environment it will be installed? Theoretical ‘line of sight’ maximum distances can be significantly longer than real world “practical” distances, especially if transmitters are located in buildings, valleys or underground. Similarly, environments where there is a lot of movement of large metal assets (e.g. forklift trucks) and/or water filled objects (ego human beings) can cause difficulties due to the constantly changing radio absorption, reflection and interference profile.


What public or shared infrastructure (e.g. cellular networks) will the data have to transit across to reach its destination. How is access control performed, and data privacy ensured?


SO, WHICH IS BEST? As you may already have realised from what has preceded, recovering data from sensors into IoT systems involves a balance of measurement performance, transmission speed, security, power, range and cost. It may not come as a big surprise therefore to learn that there is no ‘best’ solution. Wired systems typically offer the best levels of resilience and speed of acquisition, but these are increasingly becoming matched by newer fieldbus-based systems. For lower speed applications, wireless systems can offer a fast and cost- effective way to add further measurement points within an existing installation, provided they are able to operate effectively within the environment in which they are operating. They can be especially useful in overlay applications, where data is recovered from select points within existing installations, and the existing systems are not easily interfaced to third party systems. Things get more complicated when considering geographically remote data acquisition. The best technology to apply will depend not only on the factors outlined above, but also upon how many data points exist at the location. With a small number of sensors, it may be sensible to use native radio-based sensors such as those designed for networks such as NB-IoT, LoRa or SigFox. If more sensors are present, then it is more likely that some form of input aggregating edge device, accepting inputs from all sensors but passing the resulting digitised values back through a single radio channel, will be a more effective solution. This is especially true in cases where the edge device has intelligence, enabling it to provide front end filtering and transformation of the raw sensor data prior to transmission, effectively not transmitting low value repetitive data, but instead transmitting significant events which implicitly have higher value as actionable information... but that is another article. In many cases, the question should not be a case of ‘either-or’. Often, the best results are achieved by mixing technologies, optimising for each measurement point as you go. Advantech offers a range of wired and wireless sensor interfaces as both standalone devices and integrated within industrial computers and gateways. Covering the full range of available technologies including hardwired, fieldbus, serial, networked and radio via LTE, NB-IoT, mesh, and LoRaWAN, Advantech can help determine the ideal combination of devices to deploy in any application.


Advantech www.advantech.com 43


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64  |  Page 65  |  Page 66  |  Page 67  |  Page 68  |  Page 69  |  Page 70  |  Page 71  |  Page 72  |  Page 73  |  Page 74