LEAK DETECTION & INSTRUMENTATION
Myth-busting refrigerant gas detector maintenance
Tom Burniston of Samon turns some common-held beliefs about leak detectors on their head.
U
nfortunately, the refrigeration industry is like many other where gas detection is required, in that it faces a number of
potentially dangerous misconceptions that undermine the importance of adhering to manufacturers standard maintenance recommendations and guidelines. These are not mere ploys to promote calibration gas sales, but an essential part of ensuring the performance of a refrigerant leak detection system over the course of its lifetime. Several myths surrounding gas calibration contribute to confusion and misunderstanding; we are here to bust those myths. Calibration is no diff erent from a bump test – wrong. They are very diff erent things. A bump test provides an unquantifi ed validation of gas detector response, alarm functionality, and connectivity to other elements of the safety system connected to the gas detector. Calibration exposes the refrigerant sensor to a known concentration of the target gas and makes any necessary adjustments to ensure accuracy and reliability. Calibration is the same as adjustment - not true. Some sensors are extremely stable, and in the process of calibration may be proven to be within acceptable tolerances. In these instances, no adjustment is needed but the validation of calibration is still secured. Calibration is not necessary - false. Many
refrigerant sensor technologies will inherently drift over time. This can be as a result of component ageing, exposure to gas, or environmental conditions. Calibration brings the accuracy of the sensor back into the optimal tolerances and thereby extends the functional life of the sensor. For sensor technologies which claim to require no calibration, it should be noted that they are not supposed to drift – but without undergoing a calibration procedure, there is no validation that they have not. Nor does it meet industry standards if no calibration check is performed. Calibration guarantees accuracy for 12 months – no, it does not. The unfortunate
18 December 2024 •
www.acr-news.com
truth is that calibration data is only true at the time of calibration. A multitude of things could happen to a refrigerant gas sensor in the interval between maintenance procedures, include damage (physical or environmental), a poisoned sensor, or simply drift. This is why calibration and maintenance intervals should not be set for an arbitrary 12 months. Rather they should be set with respect to the risk level of the application, the sensor type, the environment, and the manufacturers guidelines. Any calibration gas can be used – not always true. Most manufacturers will recommend what calibration gas, or gases, should be used with a particular refrigerant gas detector or sensor. Important factors can include the concentration of the gas being appropriate for calibrating the range of the instrument, whether humidifi ed gas should be used, and whether a specifi c grade or
mixture of gas is required. In some instances, it can be critical whether the target calibration gas is mixed with air or with an inert gas such as nitrogen; this aff ects the basic function and operating principle of some types of refrigerant sensor. Always follow the manufacturers recommendations. Understanding, acknowledging, and busting these myths is important as it underscores the signifi cance of maintaining consistent, precise, and thorough calibration procedures for refrigerant gas detectors. Calibration serves as a cornerstone in ensuring the accuracy and reliability of these vital safety devices. However, it’s imperative to recognize that calibration alone is not suffi cient. Instead, it must be accompanied by a holistic approach to maintenance, usage, and regular checks to guarantee optimal performance.
Download the ACR News app today
Page 1 |
Page 2 |
Page 3 |
Page 4 |
Page 5 |
Page 6 |
Page 7 |
Page 8 |
Page 9 |
Page 10 |
Page 11 |
Page 12 |
Page 13 |
Page 14 |
Page 15 |
Page 16 |
Page 17 |
Page 18 |
Page 19 |
Page 20 |
Page 21 |
Page 22 |
Page 23 |
Page 24 |
Page 25 |
Page 26 |
Page 27 |
Page 28 |
Page 29 |
Page 30 |
Page 31 |
Page 32 |
Page 33 |
Page 34 |
Page 35 |
Page 36 |
Page 37 |
Page 38 |
Page 39 |
Page 40