This page contains a Flash digital edition of a book.
DATA CENTRES COOLING


LIGHTER BYTES


DigiPlex’s Air-to-Air modular data centre uses indirect evaporative cooling technology to turn this energy-hungry building type into a model of minimal consumption. Mike Simpson reports


The evaporative cooling system operates in three modes to remove heat in the most energy-efficient manner


Air-to-Air module section T www.cibsejournal.com


he DigiPlex Air-to-Air modular data centre has been developed to deliver high levels of cooling with exceptionally low power


consumption, while eliminating the risk of fire. Developed in partnership with air treatment specialist Munters and modular frame manufacturer Gardner DC Solutions, it combines indirect evaporative cooling technology with a hypoxic fire prevention system to provide an advanced, sustainable and efficient data centre solution. The Air-to-Air solution is assembled from three freestanding module types:


a white space, an electrical switchroom, and an air treatment pod (ATP). The white space module is designed to house the IT cabinets; it has a module area of 30m2


of net


usable space and incorporates a raised floor to provide a route for the chilled air to cool


the cabinet racks. The ATP provides up to 100kW of cooling to the white space. Because it is completely modular, the Air-


to-Air solution is easily scalable. Once the shell and basic infrastructure are in place, cooling units and white space modules can be procured and installed as the IT load increases. The minimum build is 100m2 based on three white space modules


, September 2013 CIBSE Journal 55


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64  |  Page 65  |  Page 66  |  Page 67  |  Page 68  |  Page 69  |  Page 70  |  Page 71  |  Page 72  |  Page 73  |  Page 74  |  Page 75  |  Page 76