Unless buildings are airtight, MVHR systems won’t be effective – which poses a particular problem in leaky, existing homes. New research by Calebre reveals the extent of that problem


Installing an MVHR system in a ‘leaky’ dwelling increases the building’s energy requirements because it increases the air change rate


T


here is a small but growing market for mechanical ventilation with heat recovery (MVHR) systems in existing homes. In 2009 it was


estimated that 15,000 units – worth £30m – were sold annually in the UK, and of these, about 5% were in the retrofit sector. However, the use of MVHR in existing


homes poses immediate questions. Installing any such system presents a technical challenge, as its effectiveness depends on striking the correct balance between optimum heat recovery, fan efficiency, air-flow rate and building airtightness. But in an existing home, airtightness


can be problematic, as it is often difficult to access and address the source of a leak – for example, if service penetrations are located behind fixed installations or constructions. As there was no information on this, an investigation was conducted by Calebre, the low-energy technology research project funded jointly by Research Councils UK Energy Programme and energy company E.ON. The findings suggest that existing homes


using MVHR must be made significantly more airtight if overall energy savings and carbon dioxide emission reductions are to be achieved.


50 CIBSE Journal September 2013


The E.ON Retrofit Test House which is being used to trial Calebre technologies


What we did The research used the E.ON Retrofit Test House (figure 1) – a replica of a 1930s semi- detached house. The case study examined the extent to which an MVHR system, fitted as part of an overall retrofit strategy, would reduce energy use and CO2


emissions.


The house was simulated, using dynamic thermal modelling software, at six levels of airtightness, expressed as air permeability values: 10, 7, 5, 3, 1 and 0.63m3


/(h.m2


@50Pa. The upper value of 10m3


/(h.m2 ) ) @50Pa


corresponds with the minimum building standards for new dwellings, and can be achieved by basic draught-proofing measures. It should be noted that air permeability values for existing homes can be higher than this. The lowest value,


www.cibsejournal.com


TIGHT Keep


IT


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64  |  Page 65  |  Page 66  |  Page 67  |  Page 68  |  Page 69  |  Page 70  |  Page 71  |  Page 72  |  Page 73  |  Page 74  |  Page 75  |  Page 76