Zinc ribbon anodes for AC mitigation
Recognising the increased need for pipeline grounding to dissipate interference.
he long-term trend in the US and many other countries is shared land use for pipelines and other utilities. Tis movement has increased the number of overhead high voltage transmission lines parallel to and sharing a corridor with an underground pipeline. Tis combination has increased the need for grounding of the pipeline to dissipate interference. In these systems, AC voltages are transmitted to the pipeline by conductive or inductive interference. Magnetic induction acts along the pipeline or pipeline segment that is about parallel to the power line and can cause significant pipeline potentials even at relatively large separation distances. Consideration must be given to safety of personnel and the public who may come into contact with above ground portions of the pipeline. Advances in interference control have resulted in the gradient control wire method. Tis method consists of one or more bare zinc conductors buried parallel to and near the pipeline and regularly connected to it. Plattline zinc ribbon anode used in this way is very effective in mitigating excessive pipeline potentials due to both inductive and conductive interference. Plattline evens out pipeline and soil potential
T
differences. Additionally, Plattline can provide cathodic protection to the pipeline. It is important to review the use and design of a gradient control wire system with an engineer experienced with this system, as its performance will depend on the multi- layered structure of the earth. For inductive interference, gradient control
wires provide additional grounding for the pipeline and decrease the induced pipe potential rise. At the same time, they raise local ground potentials, thus sharply reducing touch potentials and coating stress voltages. For conductive interference, gradient control wires dampen the soil potential rise close to the pipe while raising pipe potentials, thus providing reduced touch voltages and decreasing coating stress voltages. Life expectancy of Plattline in this application would be quite long and would generally be determined by Plattline as a projected cathodic
protection system. Te most common sizes of Plattline for AC mitigation are plus and standard. Plattline can provide a significant means to mitigate potential gradientsalong the length of a pipeline. Importance must also be placed on reducing the potentials at valve sites, metering stations, pig launchers and receivers and other accessible installations for worker safety.
Fig.1. Plattline™ zinc ribbon anodes are used in a variety of applications.
Gradient control grids or grounding mats raise local ground potentials in the same way gradient control wires do. Tese grounding mats can be made in several forms. Spiral and rectangular designs are generally standard for grounding mats. Reference should be made to NACE Standard RP0177(Latest Revision) - Recommended Practice on Mitigation of Alternating Current & Lightning Effects on Metallic Structure and Corrosion Control Systems. ●
Enter 33 or ✔ at
www.engineerlive.com/io
The Platt Brothers & Company is based in, Waterbury, CT, USA.
www.plattbros.com
www.engineerlive.com 33
Page 1 |
Page 2 |
Page 3 |
Page 4 |
Page 5 |
Page 6 |
Page 7 |
Page 8 |
Page 9 |
Page 10 |
Page 11 |
Page 12 |
Page 13 |
Page 14 |
Page 15 |
Page 16 |
Page 17 |
Page 18 |
Page 19 |
Page 20 |
Page 21 |
Page 22 |
Page 23 |
Page 24 |
Page 25 |
Page 26 |
Page 27 |
Page 28 |
Page 29 |
Page 30 |
Page 31 |
Page 32 |
Page 33 |
Page 34 |
Page 35 |
Page 36 |
Page 37 |
Page 38 |
Page 39 |
Page 40 |
Page 41 |
Page 42 |
Page 43 |
Page 44 |
Page 45 |
Page 46 |
Page 47 |
Page 48 |
Page 49 |
Page 50 |
Page 51 |
Page 52 |
Page 53 |
Page 54 |
Page 55 |
Page 56 |
Page 57 |
Page 58 |
Page 59 |
Page 60 |
Page 61 |
Page 62 |
Page 63 |
Page 64 |
Page 65 |
Page 66 |
Page 67 |
Page 68 |
Page 69 |
Page 70 |
Page 71 |
Page 72 |
Page 73 |
Page 74