Case study Fault MVA (megavolt-ampere) calculation: checking tool
Figure 1 shows an electrical system deriving a 415V three-phase 50Hz a.c. supply from a 350MVA (fault MVA) 66kV grid supply. Usuffi x
denotes the impedance voltage of the transformer and sub-transient reactance of the
standby generator in percentage. The voltage values shown are line voltage and the ratings shown against the transformers and standby generators are the full load rating of the equipment. The steps for applying the Fault MVA calculation method for the system shown in Figure 1 are as follows: Step 1: Fault MVA at location FA = 350MVA
Step 2: Fault MVA of transformer T1 = Step 3: Fault MVA of 0.1Ω 11kV distribution cable = Step 4: Fault MVA of transformer T2 = Step 5: Fault MVA of 0.01Ω 415V LV incoming cable =
MVATX Uk–Tx
MVATX Uk–Tx
Step 6: Fault MVA of generator G = Step 7: The single line diagram is then converted into an equivalent Fault MVA single line diagram (see Figure 2) Step 8: At location FA
MVAG Uk–G
= 0.7 = 4.667MVA 0.15
, the fault MVA = 350MVA, fault kA =
Step 9: At location FB the fault MVA = (∑ MVA )-1 = 1
fault kA =
MVAFault 3 x VLL
= 175.945 x 106
Step 10: When the mains is healthy, at location FC
at location FC fault kA = 3 x 11 x 103 = 9.235kA
the fault MVA = ( 1 + 1 + 1 = 7.81 x 106
MVAFault 3 x VLL
Step 11: When the mains is down and the supply at location FC
fault MVA = 4.667MVA – the result is from Step 6. Hence, at location FC
, the generator fault kA =
175.945 15.556 17.223 )-1 = 7.81MVA 3 x 0.415 x 103 = 10.867kA
is derived only from the standby generator, the
MVAFault 3 x VLL
= 4.667 x 106 3 x 0.415 x 103 = 6.493kA
Step 12: Since when the mains supply is restored, the mains and the standby generator will be running in parallel for a short period before the standby generator is taken offl ine, the distribution equipment should be designed to cope with the sum of the maximum fault currents supplied by both energy sources. Therefore, maximum designed fault kA for the switchboard and circuit breakers at location Fc should have a fault capacity not less than (10.867kA + 6.493kA)=17.36kA. Maximum fault MVA is therefore 12.48MVA.
Step 13: When the mains supply is restored, because of the short-time paralleling arrangement, fault contributions from the standby generating set need to be added to location FB
.
The fault MVA due to standby generator = therefore, at location FB
fault kA =
MVAFault 3 x VLL
( 1 + 1 + 1 = 2.971 x 106
4.667 15.556 17.223 )-1= 2.971MVA 3 x 11 x 103 = 0.156kA
Step 14: Therefore location FB should have a fault capacity not less than (9.235kA + 0.156kA)=9.391kA due to fault current contributions from the standby generator. Maximum fault MVA is therefore 178.92MVA.
Step 15: At location FA the fault current contributions from the standby generator is attenuated to 25.8A. The fault withstand capacities should not be less than 3.088kA and 353MVA.
The design check results are summarised thus: Fault location
FA Line Voltage
3-phase fault kA 3-phase fault MVA
66kV
3.088kA 353MVA
FB 11kV 9.391kA 178.92MVA FC 415V 17.36kA 12.48MVA Fault MVA Calculation results for the electrical system shown in Figure 1 58 CIBSE Journal September 2010
www.cibsejournal.com
MVAFault 3 x VLL
= 350 x 106 ( 1 + 1 + 1 3 x 66 x 103 = 3.062kA 350 500 1210)-1= 175.945MVA = 25 = 500MVA
= 0.7 = 15.556MVA 0.045
0.05 (VLL)2 ZCable
(VLL)2 ZCable
= 4152 0.01
= 17.223MVA
= 110002 0.1
= 1210MVA
Page 1 |
Page 2 |
Page 3 |
Page 4 |
Page 5 |
Page 6 |
Page 7 |
Page 8 |
Page 9 |
Page 10 |
Page 11 |
Page 12 |
Page 13 |
Page 14 |
Page 15 |
Page 16 |
Page 17 |
Page 18 |
Page 19 |
Page 20 |
Page 21 |
Page 22 |
Page 23 |
Page 24 |
Page 25 |
Page 26 |
Page 27 |
Page 28 |
Page 29 |
Page 30 |
Page 31 |
Page 32 |
Page 33 |
Page 34 |
Page 35 |
Page 36 |
Page 37 |
Page 38 |
Page 39 |
Page 40 |
Page 41 |
Page 42 |
Page 43 |
Page 44 |
Page 45 |
Page 46 |
Page 47 |
Page 48 |
Page 49 |
Page 50 |
Page 51 |
Page 52 |
Page 53 |
Page 54 |
Page 55 |
Page 56 |
Page 57 |
Page 58 |
Page 59 |
Page 60 |
Page 61 |
Page 62 |
Page 63 |
Page 64 |
Page 65 |
Page 66 |
Page 67 |
Page 68 |
Page 69 |
Page 70 |
Page 71 |
Page 72 |
Page 73 |
Page 74 |
Page 75 |
Page 76 |
Page 77 |
Page 78 |
Page 79 |
Page 80 |
Page 81 |
Page 82 |
Page 83 |
Page 84 |
Page 85 |
Page 86 |
Page 87 |
Page 88